46
HMI SETTINGS
ENGLISH
• Controller Error
High
classification
error
Low
classification
error
Errors
Error Code
Location name
Error
grade
Notes
CH10xxx
CH10001 ~
CH10010
Common
alarm
CH10001
Fire detection (smoke
detecting sensor)
1
If the fire detection contact
shorts (operates with the set
value of HMI's Smoke Control
after error indication)
CH10002
Emergency stop
detection
2
If the emergency stop contact
shorts (all operations stop after
error indication)
CH10003
HMI communication
error
2
If no communication signal is
received for more than 3
minutes
CH10004
BMS communication
error
2
If no communication signal is
received for more than 3
minutes
Others
Reserved
Reserved
CH10011 ~
CH10020
Sensor type -
Return air
CH10011
Return air thermistor
error
2
Sensor short-circuited or
disconnected
CH10012
Return air humidity
sensor error
-
Reserved
CH10013
Return air flow sensor
error
2
Sensor short-circuited or
disconnected
CH10016
Return air thermistor
faulty connection
2
Faulty connection of sensor
power and signal line
CH10017
Return air humidity
sensor faulty
connection
3
Faulty connection of sensor
power and signal line
CH10018
Return air flow sensor
faulty connection
2
Faulty connection of sensor
power and signal line
Others
Reserved
Reserved
CH10021 ~
CH10030
Sensor type -
Supply air
CH10021
Supply air thermistor
error
2
Sensor short-circuited or
disconnected
CH10022
Supply air humidity
sensor error
-
Reserved
CH10023
Supply air flow sensor
error
2
Sensor short-circuited or
disconnected
CH10026
Supply air thermistor
faulty connection
2
Faulty connection of sensor
power and signal line
CH10027
Supply air humidity
sensor faulty
connection
3
Faulty connection of sensor
power and signal line
CH10028
Supply air flow sensor
faulty connection
2
Faulty connection of sensor
power and signal line
Others
Reserved
Reserved