44
HMI SETTINGS
ENGLISH
No.
Address
Register
Data Bit
Notes
Hexadecimal
Decimal
1
0x0001
1
40002
Operation mode setting
0: not used / 1: cooling / 2:
heating / 3: dehumidification / 4:
outdoor air / 5: fan / 6: reheating
2
0x0002
2
40003
Airflow setting
0: high / 1: medium / 2: low
3
0x0005
5
40006
Target cooling temperature setting
18~30 (18) [°C] x 10
4
0x0006
6
40007
Target heating temperature setting
18~30 (30) [°C] x 10
5
0x0007
7
40008
Target cooling humidity setting
30~80 (50) [%] x 10
6
0x0008
8
40009
Target heating humidity setting
30~80 (50) [%] x 10
35
0x0022
34
40035
Return air fan (high) frequency setting
30~60 (50) [Hz]
36
0x0023
35
40036
Return air fan (medium) frequency setting
30~60 (40) [Hz]
37
0x0024
36
40037
Return air fan (low) frequency setting
30~60 (30) [Hz]
38
0x0025
37
40038
Supply air fan (high) frequency setting
30~60 (50) [Hz]
39
0x0026
38
40039
Supply air fan (medium) frequency setting
30~60 (40) [Hz]
40
0x0027
39
40040
Supply air fan (low) frequency setting
30~60 (30) [Hz]
42
0x0029
41
40042
Cooling outside air damper opening setting
Opening range (0-90) [˚]
43
0x002A
42
40043
Cooling exhaust damper opening setting
Opening range (0-90) [˚]
44
0x002B
43
40044
Cooling mixed damper opening setting
Opening range (0-90) [˚]
45
0x002C
44
40045
Heating outside air damper opening setting
Opening range (0-90) [˚]
46
0x002D
45
40046
Heating exhaust damper opening setting
Opening range (0-90) [˚]
47
0x002E
46
40047
Heating mixed damper opening setting
Opening range (0-90) [˚]
48
0x002F
47
40048
Fan outside air damper opening setting
Opening range (0-90) [˚]
49
0x0030
48
40049
Fan exhaust damper opening setting
Opening range (0-90) [˚]
50
0x0031
49
40050
Fan mixed damper opening setting
Opening range (0-90) [˚]
High
Low
• Holding Register
CAUTION
!
Abnormal operation may occur if set outside the defined range.