AHU SENSOR CONNECTION
23
ENGLISH
- Filter Differential Sensor
Ex: Filter Differential Sensor (voltage type) Connection
Item
Specification
Remark
Filter Differential
Sensor
- Power: AC 24 V
- Output signal: DC 0~10 V
- Range: 0~1 000 Pa
Optional
1. For more information on the installation of a filter differential sensor, refer to the Manual
that came with the sensor.
2. Make sure to finish all the sensor wires with a flexible tube.
3. The setting for the filter differential pressure can be changed in the setting section of the
HMI.
CAUTION
!
• Improper wiring of the sensor can damage the AHU CONTROL KIT. Make sure to check for
any incorrect wiring before turning the power on.
UI2
DC 0~10 V(Y, Feedback)
<Terminal block>
<UI module>
Ground (G0)
Ground (G0)
AC 24 V(G)
AC 24 V(G)
Summary of Contents for PAHCNM000