HMI SETTINGS
49
ENGLISH
High
classification
error
Low
classification
error
Errors
Error Code
Location name
Error
grade
Notes
CH11xxx ~
CH16xxx
CH12001 ~
CH12999
ODU 2
module error
in Comm #2
CH12255
Communication error
between ODU2 central
controls
2
Haven't received a central
control communication signal
from ODU #2 for more than 3
consecutive minutes (error
occurs only when the target
temperature control criteria is
supply air)
CH12XXX
ODU2 outdoor unit
error code is displayed
as is
2
If an error occurs in the outdoor
unit communicating with indoor
unit 2 of COM #2, the code is
displayed as is
CH13001 ~
CH13999
ODU 3
module error
in Comm #3
CH13002
ODU3 indoor sensor
(entrance pipe) error
2
Sensor short-circuited or
disconnected
CH13005
ODU3 communication
fault (indoor unit <->
outdoor unit)
2
Haven't received a
communication signal from
outdoor unit for more than 3
consecutive minutes
CH13006
ODU3 indoor sensor
(exit pipe) error
2
Sensor short-circuited or
disconnected
CH13255
Communication error
between ODU3 central
controls
2
Haven't received a central
control communication signal
from ODU #3 for more than 3
consecutive minutes (error
occurs only when the target
temperature control criteria is
supply air)
CH13XXX
ODU3 outdoor unit
error code displayed as
is
2
If an error occurs in the outdoor
unit communicating with indoor
unit 3 of COM #3, the code is
displayed as is
CH14001 ~
CH14999
ODU 4
module error
in Comm #4
CH14002
ODU4 indoor sensor
(entrance pipe) error
2
Sensor short-circuited or
disconnected
CH14005
ODU4 communication
fault (indoor unit <->
outdoor unit)
2
If indoor unit 1 of COM #4
hasn't received an outdoor unit
communication signal for more
than 3 consecutive minutes
CH14006
ODU4 indoor sensor
(exit pipe) error
2
Sensor short-circuited or
disconnected
CH14255
Communication error
between ODU4 central
controls
2
Haven't received a central
control communication signal
from ODU #4 for more than 3
consecutive minutes (error
occurs only when target
temperature control criteria is
supply air)
CH14XXX
ODU4 outdoor unit
error code displayed as
is
2
If an error occurs in the outdoor
unit communicating with indoor
unit 1 of COM #4, the code is
displayed as is