Pressure Dependent, continued.
BALANCING
Pressure Dependent
Configuration Parameter
BACnet
Function Description
Min. Position (Minimum
Damper Position)
Default Value: 10%
AV250 (R/W)
Range: 0 to 100%
Max. Cool Pos. (Maximum
Damper Position During
Cooling)
Default Value: 100%
AV251 (R/W)
Range: 0 to 100%
Max. Heat Pos. (Maximum
Damper Position During
Heating)
Default Value: 100%
AV252 (R/W)
Range: 0 to 100%
Reheat Pos. (Damper Position
During Reheating)
Default Value: 30%
AV253 (R/W)
Range: 0 to 100%
Damp. Override (Damper
Override)
Default Value: None
MV172 (R/W)
Force damper to selected position during balancing.
0 - None: No damper override. Damper under normal control.
1 - Minimum: Force damper to maintain minimum airflow setpoint.
2 - Max. cool: Force damper to maintain maximum cooling airflow setpoint.
3 - Close: Force damper closed.
4 - Reheat: Force damper to maintain maximum reheat airflow setpoint.
5 - Open: Force damper fully open.
Choices: None, Minimum, Max. Cool, Close, Reheat and Open.
Table 27: Pressure Dependent Balancing Options Screen.