MultiSITE MS8250 V
AV Room Controllers
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG Life’s Good” is a registered trademark of LG Corp.
6/9 Configuration
Standby mode
Absolute
Standby diff.
4.0 °F
Standby time
0.5 hrs
Unocc. time
0.0 hrs
Temp. occ. time 2.0 hrs
Configuration Parameters Default Value
Significance and Adjustments
Standby Mode (Standby Mode
Configuration)
Default Value: Absolute
Standby setpoints used for control.
Absolute: Standby entered values are used for standby mode.
Offset: Occupied set/- Standby diff. used for standby mode.
Refer to “Setpoints Screens” on page 49 to define Standby cool and Standby heat values.
Choices: Absolute or Offset.
Standby diff. (Standby Temperature
Differential)
Default Value: 4.0°F (2.0°C)
When Standby mode is set to “offset”, standby setpoints are calculated as follows:
Standby cool: Cool se Standby diff.
Standby heat: Heat setpoint - Standby diff.
Refer to “Setpoints Screens” on page 49 to define Standby cool and Standby heat values.
Range: 1.0°F (0.5°C) to 5.0°F (2.5°C), using 1.0°F (0.5°C) increments.
Standby Time
Default: 0.5 hours
Time between the moment where the motion sensor detects last movement in the area, and
the time which the Room Controller stand-by setpoints become active.
This parameter is not active when the “Door” function is used (wired or wireless).
Range: 0.5 to 24.0 hours, using 0.5 hour increments.
Unocc. Time (Unoccupied Time)
Default: 0.0 hours
Time between the moment where the Room Controller toggles to stand-by mode, and the
time which the Room Controller unoccupied mode and setpoints become active.
Default value of 0.0 hours disables the unoccupied timer. This prevents the Controller from being
able to switch from stand-by mode to unoccupied mode when PIR functions are used.
Range: 0.0 to 24.0 hours (0.5 hour increments).
Temp. Ccc. Time (Temporary Occupancy
Time)
Default Value: 2 hours
The time the Room Controller stays in override mode before reverting back to unoccupied
mode. When the Room Controller is in unoccupied mode, pressing the on-screen Over-
ride icon or closing the contact on UI17, configured as “Remote Override”, sets the Room
Controller to Override mode for defined time period, and uses the Occupied Cooling and
Heating setpoints.
Range: 0.0 to 24.0 hours
CONFIGURATION SCREENS
Configuration 6 / 9
Configuration 6 / 9
Figure 27:
Configuration 6 / 9 Display.
Table 20:
Configuration 6 / 9 Parameter Details.