Table 3: ZigBee Network 1 / 2 Parameter Details.
Configuration Parameters
Default Value
Significance and Adjustments
Node Type
Default Value: Router
Sets device to act as Router or Coordinator in a network.
Coord.: Creates the network and manages the binding of wireless devices.
Router: Joins a network created by a coordinator (Coordinator permit join must be set to “ON’).
Choices: Coord. or Router
PAN ID (ZigBee Pan ID)
Default Value: 0
Personal Area Network Identification that links specific Room Controllers to specific ZigBee coordinators. For
every Room Controller reporting to a coordinator, set the SAME PAN ID value both on the coordinator and the
Room Controller.
The default value of 0 is NOT a valid PAN ID and causes ZigBee to be disabled.
Range: 1 to 65535
Channel (ZigBee
Channel)
Default Value: 10
The channel (wireless frequency) on which the ZigBee network transmits and receives data. The channel of the
Coordinator must match that of the routers to exchange data.
The default value of 10 is NOT a valid channel and causes ZigBee to be disabled. The valid range of available
channels is from 11 to 25.
Using channels 15, 20, and 25 is recommended. Channel 25 is considered as being the best one because it is
furthest from the Wi-Fi channels.
Range: 10 to 25
ZigBee Network 1 / 2
The ZigBee Network screen shows only in models with onboard ZigBee.
When creating a ZigBee network, there must be one and only one device with its Node Type
set to Coordinator. For a ZigBee network with a single Room Controller (RC), the RC is set
as Coordinator to pair with the Sensor End Devices (SED). Setting the RC back to Router will
remove the paired SEDs.
For a ZigBee network with a Multi-Purpose Manager (MPM) paired to multiple RCs, the MPM is
set as Coordinator and the RCs are set as Router. The Coordinator MPM controls the pairing of
the Router RCs to the SEDs.
Before pairing any ZigBee devices, the network must first be created by the Coordinator.
NETWORK SCREENS
ZigBee Network 1 / 2
Figure 10: ZigBee Network 1 / 2 Display.
1/2 ZigBee Network
Node type
Router
PAN ID
Channel
10
Security
Low
Network Status
No NWK
Permit join
0
Off