VERTICAL-HORIZONTAL INDOOR UNITS
Acoustic Data
•
Measurement taken 3.3′ away from the unit.
• Measurements taken with no attenuation and units operating at full load normal
operating condition.
• Sound level will vary depending on a range of factors such as construction
(acoustic absorption coefficient) of particular area in which the equipment is
installed.
• Sound power levels are measured in dB(A)±3.
• Tested in anechoic chamber per ISO Standard 3745.
Figure 221:
Sound Pressure Level Measurement Location.
Table 90:
Sound Pressure Levels (dB[A]).
Figure 222:
Sound Pressure Level Diagrams.
Model No.
Sound Pressure Levels (dB[A]) (Cooling and Heating)
High Fan Speed
Medium Fan Speed
Low Fan Speed
LMVN240HV
43
42
41
LMVN360HV
45
44
43
3.3 ft.
3.3 ft.
With Case
Microphone
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (dB = 20μPa
)
10
20
30
40
50
60
70
80
63
125
250
500
1000 2000 4000 8000
Approximate
Hearing
Threshold
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Octave Band Sound Pressure Level (dB = 20μPa)
10
20
30
40
50
60
70
80
Octave Band Center Frequency (Hz)
63
125
250
500
1000 2000 4000 8000
LMVN240HV
LMVN360HV
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
160 | VERTICAL-HORIZONTAL
Multi F and Multi F MAX Indoor Unit Engineering Manual