DUCT (HIGH STATIC) INDOOR UNITS
External Static Pressure / Acoustic Data
Static Pressure (in. wg)
0.1
0.16
0.23
0.31
0.39
0.47
0.55
0.62
0.70
0.78
Model No. / Nominal Capacity
of Indoor Unit (Btu/h)
Airflow Rate / CFM
Setting Value (in. wg)
LMHN240HV
24,000
High
688
82
92
103
113
122
131
140
147
154
160
Mid
618
78
89
99
110
119
128
137
144
151
157
Low
530
73
86
96
107
116
125
134
141
148
154
LMHN360HV
36,000
High
1,130
-
124
133
140
148
154
160
-
-
-
Mid
953
-
112
122
130
137
145
152
-
-
-
Low
706
-
97
107
117
125
133
141
-
-
-
Table 59:
Sound Pressure Levels (dB[A]).
• To get the desired air flow and external static pressure combination, use the setting value from the table. Using a setting value other
than that listed in the table will not provide the desired combination.
• Table data is based at 230V. Air flow rate varies according to voltage fluctuation.
Model No.
Sound Pressure Levels (dB[A]) (Cooling and Heating)
High Fan Speed
Medium Fan
Speed
Low Fan Speed
LMHN240HV
37
36
35
LMHN360HV
44
42
40
Figure 157:
Sound Pressure Level Measurement Location.
Table 58:
Multi F Ceiling-Concealed Duct (High Static) External Static Pressure Setting Values Table.
Figure 158:
Sound Pressure Level Diagrams.
• Measurements taken with no attenuation and units operating at full
load normal operating condition.
• Sound level will vary depending on a range of factors such as
construction (acoustic absorption coefficient) of particular area in
which the equipment is installed.
• Sound power levels are measured in dB(A)±3.
• Tested in anechoic chamber per ISO Standard 3745.
4.9 ft.
6.6 ft.
3.3 ft.
DUCT
DISCHARGE
SUCTION
DUCT
Octave Band Sound Pressure Level (0dB = 20μPa)
10
20
30
40
50
60
70
80
Approximate
Hearing
Threshold
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (0dB = 20μPa)
10
20
30
40
50
60
70
80
63
125
250
500
1000 2000 4000 8000
Octave Band Center Frequency (Hz)
63
125
250
500
1000 2000 4000 8000
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
NC-15
NC-20
NC-25
NC-30
NC-35
NC-40
NC-45
NC-50
NC-55
NC-60
NC-65
Approximate
Hearing
Threshold
LMHN240HV
LMHN360HV
DUCT (HIGH STATIC) | 117
Ceiling-Concealed Duct (High Static)
Due to our policy of continuous product innovation, some specifications may change without notification.
©
LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.