background image

•  Do not cool excessively indoors. This may be harmful for your health and may consume more

electricity.

•  Block sunlight with blinds or curtains while you are operating the air conditioner.

•  Keep doors or windows closed tightly while you are operating the air conditioner.

•  Adjust the direction of the air flow vertically or horizontally to circulate indoor air.

•  Speed up the fan to cool or warm indoor air quickly, in a short period of time.

•  Open windows regularly for ventilation as the indoor air quality may deteriorate if the air condition-

er is used for many hours.

•  Clean the air filter once every 2 weeks. Dust and impurities collected in the air filter may block the

air flow or weaken the cooling / dehumidifying functions.

For your records

Staple your receipt to this page in case you need it to prove the date of purchase or for warranty 

purposes. Write the model number and the serial number here:

Model number :

Serial number :

You can find them on a label on the side of each unit.

Dealer’s name :

Date of purchase :

Here are some tips that will help you minimize the power consumption when you use the air

conditioner. You can use your air conditioner more efficiently by referring to the instructions

below:

TIPS FOR SAVING ENERGY

ENGLISH

TIPS FOR SAVING ENERGY

2

Summary of Contents for LT-C462MLE1

Page 1: ...ng the product Installation work must be performed in accordance with the national wiring standards by authorized personnel only Please retain this installation manual for future reference after reading it thoroughly TYPE CEILING CASSETTE Model LT C462MLE1 LT C512MLE1 P NO MFL42291425 ENGLISH ESPAÑOL PORTUGUESE ...

Page 2: ...condition er is used for many hours Clean the air filter once every 2 weeks Dust and impurities collected in the air filter may block the air flow or weaken the cooling dehumidifying functions For your records Staple your receipt to this page in case you need it to prove the date of purchase or for warranty purposes Write the model number and the serial number here Model number Serial number You c...

Page 3: ...Center Do not disassemble or repair the product There is risk of fire or electric shock Always ground the product There is risk of fire or electric shock Install the panel and the cover of control box securely There is risk of fire or electric shock Always install a dedicated circuit and breaker Improper wiring or installation may cause fire or electric shock Use the correctly rated breaker or fus...

Page 4: ...iciency could occur When flammable gas leaks turn off the gas and open a window for ventilation before turn the product on Do not use the telephone or turn switches on or off There is risk of explosion or fire If strange sounds or small or smoke comes from product Turn the breaker off or disconnect the power supply cable There is risk of electric shock or fire Stop operation and close the window i...

Page 5: ...the product Do not touch the metal parts of the product when removing the air filter They are very sharp There is risk of personal injury Do not step on or put anyting on the product outdoor units There is risk of personal injury and fail ure of product Always insert the filter securely Clean the filter every two weeks or more often if necessary A dirty filter reduces the efficiency of the air con...

Page 6: ... Tools 9 Installation of Indoor Outdoor Unit 16 Remote Control Preparation 17 Wiring Connection 20 Connecting Pipes to the Indoor Unit 22 Installation of Decorative Panel 24 Indoor Unit Drain Piping 27 Air Purging 29 Test running 31 Installation guide at the seaside TABLE OF CONTENTS ...

Page 7: ...INTRODUCTION ENGLISH 7 Features Filter Air Outlet Air Inlet Remote Controller INTRODUCTION ...

Page 8: ...ure Figure Name Screw driver Electric drill Measuring tape Knife Hole core drill Spanner Torque wrench Ohmmeter Hexagonal wrench Ammeter Gas leak detector Thermometer Horizontal meter Flaring tool set Manifold gauges Vacuum pump Name INSTALLATION ...

Page 9: ...ence or obstacles OUTDOOR OUTDOOR Unit Unit OUTDOOR Unit More than 300 Unit mm Installation of Indoor Outdoor Unit Selection of the best location Indoor unit There should not be any heat source or steam near the unit There should not be any obstacles to prevent the air circulation A place where air circulation in the room will be good A place where drainage can be easily obtained A place where noi...

Page 10: ...x LT C462MLE1 19 05 3 4 9 52 3 8 7 5 50 5 30 45 LT C512MLE1 19 05 3 4 9 52 3 8 7 5 50 5 30 50 Outdoor unit Indoor unit A B Outdoor unit Indoor unit A B CAUTION Rated performance for refrigerant line length of 7 5m Capacity is based on standard length and maximum allowance length is on the basis of relia bility Improper refrigerant charge may result in abnormal cycle ...

Page 11: ... position for fixing bolts slightly tilted to the drain direction after considering the direction of drain hose Drill the hole for anchor bolt on the ceiling The hole size for four anchor bolts is Ø 14 5mm 40mm depth CAUTION This air conditioner uses a drain pump Horizontly install the unit using a level gauge During the installation care should be taken not to damage electric wires Ceiling board ...

Page 12: ...flow into the suction of the air conditioner Make enough distance from a cooking room to install the air conditioner in such a place where it may not suck in oily steam 2 Avoid installing air conditioner in such circumstances where cutting oil mist or iron powder is in suspension in factories etc 3 Avoid places where inflammable gas is generated flows in is stored or vented 4 Avoid places where su...

Page 13: ...cessory Hanging bolt W3 8 or M10 Nut W3 8 or M10 Nut W3 8 or M10 Spring washer M10 Air Conditioner body Keep the length of 15 18mm between the air conditioner bottom surface and the ceiling surface Wall Indoor Outdoor Slope gradient for drain Should be 1 50 1 100 The following parts is option Hanging Bolt W 3 8 or M10 Nut W 3 8 or M10 Spring Washer M10 Plate Washer M10 Drill the piping hole on the...

Page 14: ...ement Sand Gravel for the concrete should 1 2 4 ratio The foundation surface should be finished with mortar The edges of foundation should be rounded A drain passage should be made around the foundation to thoroughly drain water away from the equipment installation area If installing the outdoor units on the roof the roof s strength have to be checked Care should be taken for weather proofing Bloc...

Page 15: ...ndoor unit This remote controller equipped with liquid crystal display If this position is higher or lower dis play is difficult to see The standard height is 1 2 1 5m high Routing of the remote controller cord Keep the remote controller cord away from the refrigerant piping and the drain piping To protect the remote controller cord from electrical noise place the cord at least 5cm away from other...

Page 16: ...rection 2 Insert the two batteries Be sure that the and directions are correct Be sure that both batteries are new 3 Re attach the cover Slide it back into position Do not use rechargeable bat teries such batteries differ from standard dry cells in shape dimensions and per formance Romove the batteries from the remote controller if the air conditioner is not going to be used for some long time ...

Page 17: ... box cover and connect the Remote controller cord and Indoor power wires Remote Controller Cable Connecting Cable 1 Phase LT C462MLE1 LT C512MLE1 Cooling Model 1 L 2 N 3 Terminal Block of Indoor Unit POWER INPUT 1 L 2 N 2 N 3 1 L Terminal Block of Outdoor Unit ...

Page 18: ... to the indoor and outdoor unit should be com plied with the following specifications Rubber insulation type H05RN F approved by HAR or SAA 20mm GN YL 45 5 10 3 WARNING Make sure that the screws of the termi nal are free from looseness Electricwire Round crimp style terminal Attach insulation sleeve Connect wires of the same gauge to both sides Model Normal Cross Sectional LT C462MLE1 LT C512MLE1 ...

Page 19: ...re and connector to meet the LOCAL REGULATION CONNECTING THE CABLE TO OUTDOOR UNIT 1 Remove the Cover control from the unit by loosening a screw Connect the wires to the terminals on the control board individually as following 2 Secure the cable onto the control board with the holder clamper 3 Refix the cover control to the original posi tion with the screw 4 Use a recognized circuit breaker betwe...

Page 20: ... copper tube in a bar or die as indi cated dimension in the table above Burrs removal Completely remove all burrs from the cut cross section of pipe tube Put the end of the copper tube pipe to down ward direction as you remove burrs in order to avoid to let burrs drop in the tubing Putting nut on Remove flare nuts attached to indoor and outdoor units than put them on pipe tube having completed bur...

Page 21: ...it After completing the piping connection be sure to check if there is gas leakage in indoor and outdoor connection Vacuum drying After completing the piping connection exe cute vacuum drying for the connecting piping and the indoor unit The vacuum drying must be carried out using the service ports of both the liquid and gas side valves Inclined Inside is shining without scratches Smooth all round...

Page 22: ...emove the Corner covers of the panel Coner cover 3 Fit the panel on the unit by inserting hooks as shown in picture 5 Fit the corner covers 4 Insert two screws on diagonal corners of panel Do not tighten the bolts completely The fixing screws are included in the indoor unit box Check the alignment of panel with the ceil ing Height can be adjusted using hanging bolts as shown in picture Insert the ...

Page 23: ...marking on PCB is as Display connector CN DISPLAY Vane control connector CN VANE 1 2 8 Close the cover for control box 9 Fit the link on the panel as shown in pic ture The link is included in the front panel unit box CN VANE 1 2 CN DISPLAY Link 10 Attach the other side of link on the filter guide of inlet grille Install the air inlet grille and filter on the panel Link Filter guide ...

Page 24: ...n on the drain piping Air conditioner unit Decorative panel Fit the insulator this part and be careful for cool air leakage Good example Ceiling board Ceiling board Decorative panel Air Cool air leakage no good Bad example Air conditioner unit CAUTION Install certainly the decorative panel Cool air leakage causes sweating Water drops fall Piping material Polyvinyl chloride pipe VP 25 and pipe fitt...

Page 25: ...ault However if it is operated for a long time in high humid atmosphere dew point tempera ture more than 23 C water drops are liable to fall In this case add heat insulation mate rial according to the following procedure Heat insulation material to be prepared Adiabatic EPDM or NBR with thickness 10 to 20mm Stick EPDM or NBR on all air conditioners that are located in ceiling atmosphere In additio...

Page 26: ...nd fix it onto the wall by saddle or equivalent 4 Tape the Pipings and Connecting cable from bottom to top 5 Form the pipings gathered by taping along the exterior wall and make the trap pre vent water from entering into the room 6 Fix the pipings onto the wall by saddle or equivalent In case of the Outdoor unit being installed below position of the Indoor unit In case of the Outdoor Unit being in...

Page 27: ...onnect the manifold valve with pressure gauge to the gas pipe side And connect the Nitrogen cylinder to the service port with charge hoses to the mani fold gauge Pressurize the system to no more than 150 P S I G with dry nitrogen gas Close the nitro gen cylinder valve when it shows reading of 150 P S I G Check for leakage with Liquid soap solution Do the leakage test at all joints of tubing indoor...

Page 28: ...uation If the system is found free from all leakages relive the nitrogen pressure by loosening the charge hose connector at nitrogen cylinder Disconnect the hose from cylinder when pressure reaches to normal state Evacuation Connect the charge hose end to the vacuum pump and evacuate the connect ing of the and indoor unit Check that the Lo knob of manifold is open Run the vac uum pump Confirm the ...

Page 29: ...ture blow out temperature wind velocity wind vol ume voltage current presence of abnormal vibration and noise operating pressure pip ing temperature compressive pressure As to the structure and appearance check following items Is the circulation of air adequate Is the draining smooth Is the heat insulation complete refrigerant and drain piping Is there any leakage of refrigerant Is the remote cont...

Page 30: ...m vibrations to which the unit is subjected during the course of transportation Check them and make sure that they are all tightly fastened If they are loose it could give rise to burn out of the wires Specification of power source Confirm that electrical capacity is suffi cient Be sure that the starting voltage is maintained at more than 90 percent of the rated voltage marked on the name plate CA...

Page 31: ...aning of the dust or salt particles stuck on the heat exchanger by using water It should be strong enough like concrete to prevent the sea wind from the sea The height and width should be more than 150 of the outdoor unit It should be keep more than 70 cm of space between outdoor unit and the windbreak for easy air flow CAUTION Air conditioners should not be installed in areas where corrosive gase...

Page 32: ...32 ENGLISH ...

Page 33: ......

Reviews: