10
INSTALLATION
ENGLISH
Piping length and the elevation
Model
Pipe Size
mm(inch)
Length A(m)
Elevation B(m)
*Additional
refrigerant
(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
LT-C462MLE1 19.05(3/4”) 9.52(3/8”)
7.5
50
5
30
45
LT-C512MLE1 19.05(3/4”) 9.52(3/8”)
7.5
50
5
30
50
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
CAUTION
• Rated performance for refrigerant line length of:7.5m
• Capacity is based on standard length and maximum allowance length is on the basis of relia-
bility.
• Improper refrigerant charge may result in abnormal cycle.
!