PIPE CONNECTION
ENGLISH
21
Capacity
(Btu/h)
Pipe Size
mm(inch)
Length A(m)
Elevation B(m)
*Additional
refriger-
ant(g/m)
Gas
Liquid
Standard
Max.
Standard
Max.
70k
22.2(7/8)
9.52(3/8)
7.5
100
0
30
61
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
• The standard pipe length is 7.5m. If the pipe length exceeds 7.5m, Need to additional
charge of the refrigerant which according to the table.
• If 72kBtu/h model is installed at a distance of 100m 5,550g of refrigerant should be added
(100-7.5)x61g = 5,643g
• Capacity is based on standard length and maximum allowance length is on the basis of reli-
ability.
• Improper refrigerant charge may result in abnormal cycle.
CAUTION
!
Pipe length and the elevation
PIPE CONNECTION