14
PRODUCT INSTALLATION
ENGLISH
- Insert the set anchor and washer onto the
suspension bolts for locking the suspension
bolts on the ceiling.
- Mount the suspension bolts to the set
anchor firmly.
- Secure the installation plates onto the sus-
pension bolts (adjust level roughly) using
nuts, washers and spring washers.
• Local supply
①
Set anchor
②
Plate washer - M10
③
Spring washer - M10
④
Nut - W3/8 or M10
⑤
Suspension bolt - W3/8 or M10
1 Set anchor
Old building
New building
2 Plate washer
3 Spring washer
4 Nut
5 Suspension
bolts
Tighten the nut and bolt to prevent unit
falling.
CAUTION
!
Install declination of the indoor unit is
very important for the drain of the duct
type air conditioner. Always lay the in-
door unit with downward inclination
(0.8 ˚ to 1.3 ˚). Prevent any upward flow
or reverse flow in any part.
CAUTION
!
Ceiling
15mm~25mm
0.8 ˚~1.3 ˚
Drainage hole
Ceiling
Drainage hole
Ceiling
Drainage hole
CORRECT
INCORRECT
Summary of Contents for B70AWYN985