SETTING & TEST
ENGLISH
45
Display
Title
Cause of Error
Outdoor unit related error
4
9
1
Outdoor Unit Faulty IPM
Temperature Sensor
Outdoor Unit IPM Temperature Sensor
short/open
5
0
1
Omitting connection of R, S, T
power of Outdoor Unit
Omitting connection of outdoor unit
5
2
1
Transmission error : inverter PCB
’
Main PCB
Failing to receive inverter signal at main PCB of
Outdoor Unit
5
3
1
Transmission error : indoor unit
’
main PCB of Outdoor Unit
Failing to receive indoor unit signal at main PCB of
Outdoor Unit .
5
4
1
Reverse connection of R, S, T
power of Outdoor Unit
Reverse connection or omitting connection of R,
S, T power of Outdoor Unit
5
7
1
Outdoor Unit Communication Error
with Inverter Controller
Outdoor Unit Controller part cannot receive invert-
er control signals (usually happens after on-board-
ing)
6
0
1
Inverter PCB EEPROM Error of
Outdoor Unit
Access Error of Inverter PCB of Outdoor Unit
6
7
1
Outdoor Unit Fan Lock
Restriction of Outdoor Unit
7
3
1
Instant Over Current(Peak) of
Outdoor Unit PFC
Instant Over Current(Peak) of Outdoor Unit PFC
7
5
1
Outdoor Unit Fan CT Sensor Error
Outdoor Unit Fan CT Sensor open or short
7
6
1
Outdoor Unit Fan DC Link High
Voltage Error
Outdoor Unit Fan DC Link High Voltage Error
7
7
1
Outdoor Unit Fan Over Current
Error
Outdoor Unit Fan Current is over 5A
7
9
1
Outdoor Unit Fan Start Failure Error
Outdoor Unit Fan First Position Sensing Failure
Summary of Contents for B70AWYN985