Troubleshooting Guide
Service Manual 99
■
Error Indicator
The function is to self-diagnoisis airconditioner and express the troubles identifically if there is any trouble.
If more than two troubles occur simultaneously, primarily the highest trouble fo error code is expressed.
After error occurrence, if error is released, error LED is also released simultaneously.
Having or not of error code is different from Model.
■
ERROR display
• Error display method is classified depending on method and frequencies of flickering as example:
ex) ERROR CODE = 45
Number of "10" cipher "4"= Flickers lengthily 4 times.
Number of "1" cipher "5"= Flickers shortly 5 times.
■
Countermeasure of error occurred
1) For error as described in above item
~
,
): Stops operation of the outdoor unit
Transmits error code to the indoor unit.
2) For error as described in above item 4): Transmits error code to the indoor unit
• For thermister error, error terminates after powering off.
• Excess of capacity (Where capacity of the outdoor unit differs from capacity of the indoor unit Error display)
3) Error of the discharge temperature sensor is processed in following method:
For sensor open process, check 4 minutes after COMP operation and 10 minutes after power application.
For short process, check and process from the time when power is applied.
Outdoor unit, outdoor temperature Thermister open/short .........................................................................44
Outdoor unit pipe temperature Thermister open/short ...............................................................................45
Excess of capacity (inconsistency with option capacity setup in outdoor unit)............................................51
Communication between indoor unit and outdoor unit in-available ..............................................................5
D-Pipe Temperature High ...............................................................................................33
D-Pipe thermister open/short ......................................................................................................................47
Outdoor unit suction temperature Thermister open/short ...........................................................................48
■
Type and code of indoor unit error
[ERROR CODE]
No Error .......................................................................................................................................................01
Indoor Room themistor error .......................................................................................................................01
Indoor in-piping sensor error .......................................................................................................................02
Remote controller error................................................................................................................................03
Drain Pump error .........................................................................................................................................04
Communcation error between in and out ....................................................................................................05
Indoor Out-Piping sensor error ....................................................................................................................06
Different mode operation .............................................................................................................................07
■
Type and code of outdoor unit error
[ERROR CODE]
Self-diagnosis Function
Summary of Contents for ATNH126ELFB
Page 68: ...72 Universal System Air Conditioner II Outdoor Units Introduction 73 MPS Variable SINGLE A 75 ...
Page 82: ...86 Universal System Air Conditioner MPS Variable SINGLE A 4 Wiring Diagrams AUUH126B AUUH186B ...
Page 83: ...MPS Inverter SINGLE A Service Manual 87 AUUH246B AUUH306B ...
Page 84: ...MPS Inverter SINGLE A 88 Universal System Air Conditioner AUUH368B AUUH488B ...
Page 85: ...Service Manual 89 MPS Variable SINGLE A AUUH608B ...
Page 104: ...Electronic Control Device 108 Universal System Air Conditioner Ceiling Duct Type BH Series ...
Page 105: ...Electronic Control Device Service Manual 109 BG BR Series ...
Page 106: ...Electronic Control Device 110 Universal System Air Conditioner VE Series Ceiling Floor ...
Page 107: ...Electronic Control Device Service Manual 111 VB Series ...
Page 109: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Page 110: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Page 111: ...Schematic Diagram Service Manual 115 Ceiling Floor ...
Page 151: ...P No 3828A22009F Printed in Korea ...