96 Universal System Air Conditioner
MPS Variable SINGLE A
8.3 Piping length and the elevation
• Capacity is based on standard length and maximum allowance length is on the basis of reliability.
• Improper refrigerant charge may result in abnormal cycle.
• Oil trap should be installed every 10 meters.
CAUTION
Outdoor unit
Indoor unit
A
B
Outdoor unit
Indoor unit
A
B
A
Oil trap
Outdoor unit
Indoor unit
B
Gas
Liquid
Standard
Max.
Standard
Max.
Capacity
12k Btu/h
3/8"
(9.52mm)
1/4"
(6.35mm)
7.5
15
5
5
20
18k Btu/h
1/2"
(12.7mm)
1/4"
(6.35mm)
7.5
50
5
30
35
24k Btu/h
1/2"
(12.7mm)
1/4"
(6.35mm)
7.5
50
5
30
35
36k Btu/h
5/8"
(15.88mm)
1/4"
(6.35mm)
7.5
50
5
30
40
48k Btu/h
3/4"
(19.05mm)
3/8"
(9.52mm)
7.5
50
5
30
75
(Chargeless 30m)
60k Btu/h
3/4"
(19.05mm)
3/8"
(9.52mm)
7.5
50
5
30
80
(Chargeless 30m)
30k Btu/h
❈
Extra refrigerant = (Extended length - Rated length) x Additional refrigerant.
5/8"
(15.88mm)
1/4"
(6.35mm)
7.5
50
5
30
35
Pipe Size
Length (m)
Elevation (m)
*Additional
(Diameter:Ø)
refrigerant(g/m)
8.4 Refrigerant Additional Charging Method
(Except: AUUH126B / 186B / 246B / 306B / 368B)
There is not additional charging of refrigerant by main pipe of 30m below.
For additional charging method, see below table.
* Example(AUUH608B)
*(L1=Main Pipe)
Single
Refrigerant=(L1-30)*0.08
Summary of Contents for ATNH126ELFB
Page 68: ...72 Universal System Air Conditioner II Outdoor Units Introduction 73 MPS Variable SINGLE A 75 ...
Page 82: ...86 Universal System Air Conditioner MPS Variable SINGLE A 4 Wiring Diagrams AUUH126B AUUH186B ...
Page 83: ...MPS Inverter SINGLE A Service Manual 87 AUUH246B AUUH306B ...
Page 84: ...MPS Inverter SINGLE A 88 Universal System Air Conditioner AUUH368B AUUH488B ...
Page 85: ...Service Manual 89 MPS Variable SINGLE A AUUH608B ...
Page 104: ...Electronic Control Device 108 Universal System Air Conditioner Ceiling Duct Type BH Series ...
Page 105: ...Electronic Control Device Service Manual 109 BG BR Series ...
Page 106: ...Electronic Control Device 110 Universal System Air Conditioner VE Series Ceiling Floor ...
Page 107: ...Electronic Control Device Service Manual 111 VB Series ...
Page 109: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Page 110: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Page 111: ...Schematic Diagram Service Manual 115 Ceiling Floor ...
Page 151: ...P No 3828A22009F Printed in Korea ...