Ceiling Concealed Duct
70 Universal System Air Conditioner
Ceiling
CAUTION
1~3mm
Drainage hole
Drainage hole
U-Trap
B
C
A
≥
70mm
B
≥
2C
C
≥
2 x SP
SP = External Pressure
(mmAq)
Ex) External Pressure
= 10mmAq
A
≥
70mm
B
≥
40mm
C
≥
20mm
A
Make sure to be closed.
Unit
Drainage pipe
(Local supply)
Thermal insulator
(Local supply)
Drainage hole
CAUTION FOR GRADIENT OF
UNIT AND DRAIN PIPING
Lay the drain hose with a downware
inclination so water will drain out.
MAX 700mm
Drain Pipe
Drain Pump
1/50~1/100
1/50~1/100
Front of view
• Alway lay the drain with downward inclination
(1/50 to 1/100).
Prevent any upward flow or reverse flow in any
part.
• 5mm or thicker formed thermal insulator shall
always be provided for the drain pipe.
CORRECT
• Install the P-Trap (or U-Trap) to prevent
a water leakage caused by the blocking
of intake air filter.
Applied U-Trap Dimension
1. Decline Installation of indoor unit is very important for the drain of the duct type air conditioner.
2. Minimum thickness of the insulation for the connecting pipe should be 5mm.
• The unit must be or declined to wards drain hose while installation.
CORRECT
INCORRECT
INCORRECT
Summary of Contents for ATNH126ELFB
Page 68: ...72 Universal System Air Conditioner II Outdoor Units Introduction 73 MPS Variable SINGLE A 75 ...
Page 82: ...86 Universal System Air Conditioner MPS Variable SINGLE A 4 Wiring Diagrams AUUH126B AUUH186B ...
Page 83: ...MPS Inverter SINGLE A Service Manual 87 AUUH246B AUUH306B ...
Page 84: ...MPS Inverter SINGLE A 88 Universal System Air Conditioner AUUH368B AUUH488B ...
Page 85: ...Service Manual 89 MPS Variable SINGLE A AUUH608B ...
Page 104: ...Electronic Control Device 108 Universal System Air Conditioner Ceiling Duct Type BH Series ...
Page 105: ...Electronic Control Device Service Manual 109 BG BR Series ...
Page 106: ...Electronic Control Device 110 Universal System Air Conditioner VE Series Ceiling Floor ...
Page 107: ...Electronic Control Device Service Manual 111 VB Series ...
Page 109: ...Schematic Diagram Service Manual 113 Ceiling Cassette Type ...
Page 110: ...Schematic Diagram 114 Universal System Air Conditioner Ceiling Duct Type ...
Page 111: ...Schematic Diagram Service Manual 115 Ceiling Floor ...
Page 151: ...P No 3828A22009F Printed in Korea ...