20
MUL
TI V W
ater Mini System Installation Manual
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. “LG” is a registered trademark of LG Corp.
All referenced materials are to be field-supplied. Images are not to scale, are for reference only, and are not intended to be used for design
purposes.
• Securely fasten all four (4) corners to the
supporting base.
• If not otherwise directed by the structural
engineer or local codes, Use a 7/16 inch or
1/2 inch diameter J-bolt. Use a hexagon nut
with a spring washer.
• Include anti-vibration material chosen by the
acoustics engineer.
• Include enough space for refrigerant piping
and electrical wiring when installing through
the bottom of the unit.
• Use an H-beam, concrete support, or other
acceptable support structure designed by a
structural engineer.
Unit: Inch
8
8
Nut
3
3
Spring Washer
Unit Mounting
Foot
Anti-vibration
Material
Four Bolts
Required
H-Beam
Concrete
Base
4
Three Threads
Note:
Figure 10: Close up of Anchor Bolts.
Location of the
anchor bolts
13-15/16
15-1/4
Unit: Inch
Fron
t
Figure 9: Location of the Anchor Bolts.
•
When building a base support for the water source unit, ensure that the floor surface / location has enough strength to support the
weight of the unit, and enough space for pipes and wiring.
•
Install the water source unit to a base and in a manner approved by the structural engineer to minimize damage to the unit in the event
of an earthquake. Any deficiency in installation may cause unit to fall, resulting in physical injury or death.
Anchoring the Water Source Unit
General Mounting
Securely attach the water source unit to a concrete pad, base rails, or other mounting platform that is anchored to the building structure.
Avoid placing the unit in a low lying area where water may accumulate. Refer to dimensional drawing in the “Product Data” section on page
10, and follow the applicable local code for clearance, mounting, anchor, and vibration attenuation requirements.
General Mounting / Anchoring the Water Source Unit
INSTALLATION
Plan View
Side View