50 Room Air Conditioner
Troubleshooting Guide
Additional gas charging
(Gas leakage)
• When refrigerant is insufficient by leakage, recharge the unit with the refrigerant up to normal oper-
ating suction pressure.
• Use the graph or the equation below to get operating suction pressure according to indoor and out-
door temperature.
Suction pressure was measured at 3-way valve service port after operating the unit for 10 minutes.
The method of using graph
- Find outdoor temperature.
- Find indoor temperature onto the curve of outdoor temperature.
- Read suction pressure at the axis of ordinates.
The method of using equation
-. Calculate suction pressure after putting indoor and outdoor temperature into the equation.
13
(At operating the Unit for 10 minutes)
Suction Pressure
(Kg/cm
2
.g)
Outdoor Temp.
(˚
C)
Indoor Temp. (˚C)
12
11
10
9
8
7
6
5
5
10
15
20
25
30
35
40
50˚C
40˚C
30˚C
20˚C
10˚C
0˚C
P = 3 + 0.0123 x T
out
1.5
+ 0.8 x T
in
0.5
Where, P
: Suction Pressure(kg/cm
2
.g)
Tout : Outdoor Temperature(˚C)
Tin
: Indoor Temperature(˚C)
Operating Suction Pressure (For R410A)
(According to Indoor & Outdoor Temperature)
Summary of Contents for Art Cool LS090CE
Page 62: ...62 Room Air Conditioner Schematic Diagram Schematic Diagram Electric Control Device Indoor ...
Page 63: ...Service Manual 63 Schematic Diagram Outdoor 9k 12k ...
Page 64: ...64 Room Air Conditioner Outdoor 18k 24k ...
Page 65: ...Service Manual 65 Wiring Diagram Indoor Unit Models 9k 12k 18k 24k ...
Page 67: ...Service Manual 67 Models 18k C O Models 18k H P 24k C O H P Schematic Diagram ...
Page 69: ...Service Manual 69 Outdoor 9k 12k TOP VIEW BOTTOM VIEW Schematic Diagram ...
Page 70: ...70 Room Air Conditioner Schematic Diagram Outdoor 18k 24k TOP VIEW BOTTOM VIEW ...