54 Room Air Conditioner
Troubleshooting Guide
The product is not operate with the remote controller.
Turn on Main Power
While the compressor has been stopped, the compressor does not
operate owing to the delaying function for 3 minutes after stopped.
Caused by other parts except the remote controller
Cause by the remote controller
When the mark( ) is displayed in LCD screen, replace
battery.
Check the contact of CN-DISP connector.
When the compressor stopped Indoor Fan is driven by a low speed.
At this point the wind speed is not controlled by the remote controller.
(When operated in the Sleeping Mode, the wind speed is set to the
low speed by force.)
Check DISP PWB Ass'y
- Voltage between CN DISP
-
: DC +5V
When the detect switch(double key) inside the remote
controller door is fault, it is impossible to operate
temperature regulating( / ) and wind speed selecting.
Check the connecting circuit between the remote controller
MICOM (No. ) - R17(2
Ω
) - IR LED - Q1 - R16(2.2K
Ω
).
Check point
• Check the connecting circuit between PIN
43
-
R11L(1K) - C11L(680PF) - MICOM PIN
• Check Receiver Ass'y
Summary of Contents for Art Cool LS090CE
Page 62: ...62 Room Air Conditioner Schematic Diagram Schematic Diagram Electric Control Device Indoor ...
Page 63: ...Service Manual 63 Schematic Diagram Outdoor 9k 12k ...
Page 64: ...64 Room Air Conditioner Outdoor 18k 24k ...
Page 65: ...Service Manual 65 Wiring Diagram Indoor Unit Models 9k 12k 18k 24k ...
Page 67: ...Service Manual 67 Models 18k C O Models 18k H P 24k C O H P Schematic Diagram ...
Page 69: ...Service Manual 69 Outdoor 9k 12k TOP VIEW BOTTOM VIEW Schematic Diagram ...
Page 70: ...70 Room Air Conditioner Schematic Diagram Outdoor 18k 24k TOP VIEW BOTTOM VIEW ...