Troubleshooting Guide
Trouble analysis
1. Check temperature difference between intake and discharge air and operating current.
Temp. Difference
Temp. difference : approx. °F(0°C)
Current : less than 80% of
rated current
Temp. difference : approx. 14°F(8°C)
Current : less than 80% of
rated current
Temp. difference : less than 14°F(8°C)
Current : over the reated
current
Temp. difference : over 14°F(8°C)
Operating Current
• All amount of refrigerant leaked
out. Check refrigeration cycle.
• Refrigerant leakege
Clog of refrigeration cycle
Defective compressor
• Excessive amount of refrigerant
• Normal
Temperature difference between intake and discharge air depends on room air humidity. When the room air
humidity is relativery higher, temperature difference is smaller. When the room air humidity is relatively lower
temperature difference is larger.
2. Check temperature and pressure of refrigeration cycle.
1. The suction pressure is usually 8.5~9.5 kg/cm
2
G(Cooling) at normal condition.
2. The temperature can be measured by attaching the thermometer to the low pressure tubing and wrap it with
putty.
NOTICE
NOTICE
Suction pressure
Temperature
(Compared with
(Compared with
Cause of Trouble
Description
the normal value)
the normal valve)
Defective compressor
Current is low.
Defective 4-way reverse valve
Excessive amount of
High pressure does not quickly
Normal
refrigerant
rise at the beginning of
operation.
Insufficient amount of
Current is low.
Lower Higher
refrigerant
(Leakage)
Clogging
Current is low.
High
Higher
Cycle Parts
Summary of Contents for Art Cool LS090CE
Page 62: ...62 Room Air Conditioner Schematic Diagram Schematic Diagram Electric Control Device Indoor ...
Page 63: ...Service Manual 63 Schematic Diagram Outdoor 9k 12k ...
Page 64: ...64 Room Air Conditioner Outdoor 18k 24k ...
Page 65: ...Service Manual 65 Wiring Diagram Indoor Unit Models 9k 12k 18k 24k ...
Page 67: ...Service Manual 67 Models 18k C O Models 18k H P 24k C O H P Schematic Diagram ...
Page 69: ...Service Manual 69 Outdoor 9k 12k TOP VIEW BOTTOM VIEW Schematic Diagram ...
Page 70: ...70 Room Air Conditioner Schematic Diagram Outdoor 18k 24k TOP VIEW BOTTOM VIEW ...