Service Manual 55
Troubleshooting Guide
Compressor/Outdoor Fan are unable to drive.(9k Model)
Turn on Main Power
Operate "Cooling Mode( )" by setting the desired temperature of the
remote controller is less than one of the indoor temperature by 2°F at least.
When in Fan Mode, Compressor/Outdoor Fan is stopped.
Check the sensor for indoor temperature is attached as close as to be
effected by the temperature of Heat Exchanger(EVA).
When the sensor circuit for indoor temperature and connector are in bad
connection or are not engaged, Compressor/Outdoor Fan is stopped.
• Check the related circuit of R02H(12.1K), R04H(6.2K), Micom (No.27)
(Indoor unit).
• Check the indoor temperature sensor is disconnected or not(About 10k
Ω
/ at 77°F).
When the temperature around Outdoor PWB Ass'y is above 163°F the
compressor is stop and only Outdoor Fan is operating.
Turn off Main Power
• Check the electrical wiring diagram of outdoor side.
• Check the abnormal condition for the component of Compressor/Outdoor
Fan Motor.
Check Relay(RY - COMP) for driving compressor.
• When the power(About AC110V) is applied to the connecting wire termi-
nal support transferred to compressor, PWB Ass'y is normal.
• Check the circuit related to the relay(Outdoor unit).
Check point
COMP ON
COMP OFF
Between Micom(No.
DC5V
DC0V
5) and GND
Between IC01M, IC02M(No. 9)
Below DC 1V
About DC12V
and IC01M, IC02M(No. 8)
(app)
Summary of Contents for Art Cool LS090CE
Page 62: ...62 Room Air Conditioner Schematic Diagram Schematic Diagram Electric Control Device Indoor ...
Page 63: ...Service Manual 63 Schematic Diagram Outdoor 9k 12k ...
Page 64: ...64 Room Air Conditioner Outdoor 18k 24k ...
Page 65: ...Service Manual 65 Wiring Diagram Indoor Unit Models 9k 12k 18k 24k ...
Page 67: ...Service Manual 67 Models 18k C O Models 18k H P 24k C O H P Schematic Diagram ...
Page 69: ...Service Manual 69 Outdoor 9k 12k TOP VIEW BOTTOM VIEW Schematic Diagram ...
Page 70: ...70 Room Air Conditioner Schematic Diagram Outdoor 18k 24k TOP VIEW BOTTOM VIEW ...