Troubleshooting Guide
- 88 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
Is EEV head(Coil)
assembly normally?
Change EEV assembly
Yes
Yes
Yes
No
Yes
No
No
No
Is EEV connector
connected normally?
Is there indoor unit
which leaks ref.
much
1)
?
Is SC EEV or SC
circuit leaks?
Change SC EEV or SC EEV
assembly
Assemble again or change
EEV head(coiL)
Connect EEV connector
Check liquid pipe
– gas pipe direct connection
N
T
S
R
T
S
R
* Measuring input voltage
* Noise filter wiring
R(L1)
S(L2)
T(L3)
N
1) Ref. leakage much
: Both Pipe in, pipe out temp. is under 10℃
during unit is off(EEV 40pls)
Also, big refrigerant flow noise occured
n
Error diagnosis and countermeasure flow chart
Error No.
Error Type
Error Point
Main Reasons
1501
Discharge superheat
low
Discharge
superrheat is
under 3℃
(liquid back)
Check liquid bypass
1. Individual power of indoor unit is open during
operation
2. Indoor unit EEV fault(ref. leak much)
3. Indoor unit EEV connector disconnected.
4. SC EEV fault(ref. leak much)
5. Liquid pipe – gas pipe direct connection