Troubleshooting Guide
- 65 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
281
Inverter DC link high
voltage error
Error
No.
Error Type
Error Point
Main Reasons
Inv PCB DC link voltage
supplied over 780V
1. Input voltage abnormal (R,S,T,N)
2. Inv. PCB damage
(DC Link voltage sensing part)
n
Error Diagnosis and Countermeasure Flow Chart
Is input voltage normal?
No
Yes
Recheck power and installation condition
Check
R~S/S~T/T~R phase voltage is 380V 10%
R~N/S~N/T~N phase voltage is 220V 10%
→
Check connection condition and wiring if power is
abnormal
Is Inv. PCB
normal?
No
Yes
Replace Inv. PCB
1. Check R/S/T/N wiring conditions
2. Check Noise filter wiring conditions
→
Rewire them if abnormality found.
No
Yes
Replace Inv. PCB
Is Inv. PCB normal?
No
Yes
* Measuring input voltage
* Noise filter wiring
Are there any power wire
connections normal?
N
T
S
R
T
S
R