Troubleshooting Guide
- 75 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
1. 130% more than Compressor Module rated
capacity
2. Wrong connection of transmission
cable/piping
3. Detect ot Compressor Module PCB
Error
No.
Error Type
Error Point
Main Reasons
Sum of indoor unit
capacity exceed
Compressor Module
capacity specification
Over-Capacity
(Sum of indoor unit
capacity is more than
outdoor capacity)
511
n
Error diagnosis and countermeasure flow chart
Is capacity sum of
indoor units less than
130% of Compressor module
capacity at LGMV?
No
Yes
Are quantity and capacity
of indoor units installed
same as the data of LGMV?
Yes
Adjust the capacity of indoor
and Compressor module
No
Check communication cables
between indoor and
Compressor module
End