Troubleshooting Guide
- 71 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
n
Error diagnosis and countermeasure flow chart
Sensor connection to PCB
is normal?
Is the resistance of
sensor normal?*
Insert sensor connector to PCB properly
Replace sensor
Replace corresponding outdoor PCB
Yes
No
No
Is sensor resistance
value same as temperature
value of LGMV?
Yes
Yes
No
Replace corresponding sensor
* Error is generated if the resistance is more than 5M(open) and less than 2k (short)
Note: Standard values of resistance of sensors at different temperatures (5% variation)
10C = 362k : 25C= 200k : 50C= 82k : 100C= 18.5k
Check the resistance
inverter compressor
discharge temperature
sensor
Error No.
Error Type
Error Point
Main Reasons
411
Compressor1
discharge pipe
temperature sensor
error
Sensor measurement
value is abnormal
(Open/Short)
1. Defective connection of the compressor1 discharge
pipe temperature sensor
2. Defective discharge pipe compressor sensor of the
compressor1 (open/short)
3. Defective outdoor PCB