Installation of Venting for
Outdoor Units
Follow Guidelines
All of the following guidelines must be followed when
installing the unit.
WARNING
Do not install units in locations where flue products
can be drawn into adjacent building openings such
as windows, fresh air intakes, etc. Distance from
vent terminal to adjacent public walkways, adjacent
buildings, operable windows and building openings
shall conform with the local codes. In the absence
of local codes, installation shall conform with the
National Fuel Gas Code, ANSI Z223.1 or the Canadian
CAN/CGA B-149 Installation Codes.
WARNING
The following guidelines must be followed for all
outdoor units:
1. Building materials that will be affected by flue
gases should be protected.
2. Maintain minimum horizontal clearance of 4 feet
from electric meters, gas meters, regulators
and relief equipment. In Canada, the minimum
clearance is 6 feet.
3. The combustion blower discharge on outdoor
units must be located a minimum of 42 inches
from any combustible materials.
4. Do not modify or obstruct the combustion air inlet
cover or the combustion blower weatherhood.
5. Do not add vents other than those supplied by the
manufacturer.
6. During the winter, keep the unit clear of snow to
prevent any blockage of the combustion venting.
Install Stack (optional)
Clearance may require an exhaust stack. Install an
exhaust stack as needed to the exhaust connection on
the unit. Install a vent terminator on the exhaust pipe.
Exhaust transition and vent termination must be
purchased from the factory for proper operation.
Exhaust pipe is by others.
Installation of Venting for
Indoor Units
WARNING
The following guidelines must be followed for all indoor
units:
1. Installation of venting must conform with local
building codes. In the absence of local codes,
installation must conform with the National Fuel
Gas Code, ANSI Z223.1 or in Canada, CAN/
CGA-B149 installation codes.
2. For the exhaust pipe, use pipe approved for a
Category III appliance or galvanized vent pipe sized
26 gauge or heavier. The piping is required to be
gas-tight by ANSI.
3. For the combustion air pipe on separated
combustion units, sealed single-wall galvanized air
pipe is recommended.
4. The joints must be sealed with a metallic tape or
Silastic™ suitable for temperatures up to 350°F.
5. A minimum of 12 inches of straight vent pipe is
recommended after the exhaust connection and
before any elbows.
6. Vertical combustion air pipes should be fitted with
a tee, drip leg and clean-out cap to prevent any
moisture in the combustion air pipe from entering
the unit.
7. To reduce condensation, insulate any vent runs
greater than 5 feet.
8. All vent pipe connections should be made with at
least three corrosion-resistant sheet metal screws.
9. Refer to the National Fuel Gas Code for additional
piping guidelines.
NOTE
Vent piping is supplied by others and not supplied by
manufacturer.
NOTE
The drip leg should be cleaned out periodically during
the heating season.
NOTE
Clearances from combustible material for indoor units
are determined by the National Fuel Gas Code and/or
other local codes.
Summary of Contents for AR-DE12-05A
Page 75: ...Gas Supply In Typical Split Burner Manifold ...
Page 94: ...NOTE For HMA gas furnace for 311 and 352 chassis see separate IOM Manual ...
Page 96: ...HANDHELD KEYPAD DISPLAY OPTIONAL ...
Page 105: ......
Page 107: ......
Page 108: ......
Page 109: ......
Page 110: ......
Page 111: ......
Page 112: ......
Page 113: ......
Page 114: ......
Page 115: ......
Page 116: ......
Page 117: ......
Page 118: ......
Page 119: ......
Page 120: ......
Page 121: ......
Page 122: ......
Page 123: ......
Page 124: ......
Page 125: ......
Page 126: ......
Page 127: ......
Page 128: ......
Page 129: ......
Page 130: ...Controls Sequence of Operation ...
Page 131: ......
Page 132: ......
Page 133: ......
Page 134: ......
Page 135: ......
Page 136: ......
Page 137: ......
Page 138: ......
Page 139: ......
Page 140: ......
Page 141: ......
Page 142: ......
Page 143: ......
Page 144: ......
Page 145: ......
Page 146: ......
Page 147: ......
Page 148: ......
Page 149: ......
Page 150: ......
Page 151: ......
Page 152: ......
Page 153: ......
Page 154: ......
Page 155: ......
Page 156: ......
Page 157: ......
Page 158: ......
Page 159: ......
Page 160: ......
Page 161: ......
Page 162: ......
Page 163: ......
Page 164: ......
Page 165: ......
Page 166: ......
Page 167: ......
Page 168: ......
Page 169: ......
Page 170: ......
Page 171: ......
Page 172: ......
Page 173: ......
Page 174: ......
Page 175: ......
Page 176: ......