![Leviton Z-MAX r24sd User Manual Download Page 69](http://html1.mh-extra.com/html/leviton/z-max-r24sd/z-max-r24sd_user-manual_1885704069.webp)
Photocells, Photocell Wiring
Z-MAX Remote Relay Panel User Guide, Revision A 8/2005
PK-93194-10-00-0A
Page 63
Photocells
The relay cabinet is capable of supporting the following types of
photocells:
•
Switched Photocell (On/Off, trigger point set at photocell)
•
0-10V Photocell
The configuration and behavior of your photocell is set via
software and discussed elsewhere. This seciton only covers
installation.
Photocell Wiring
Step 1:
Connect leads per wiring diagram as illustrated in
one of the figures below:
0-10VDC Photocell Wiring
IN +V COM
Terminal order/function may differ from
that shown. Confi rm on cabinet circuit
board or I.D. label.
IN +V COM
Common
(DC Ground)
Power (+24VDC)
Control Signal
(+0-10VDC)
PhotoCell
Terminal order/function may differ from
that shown. Confi rm on cabinet circuit
board or I.D. label.