Master/Slave Network Topology,
Z-MAX Remote Relay Panel User Guide, Revision A 8/2005
PK-93194-10-00-0A
Page 25
•
(4) Remote #3, (4) relays, relay numbers 65-68
In order to achieve this configuration, the following configuration
changes must be made:
1
The number of local relays, a setting under Global
Defaults on the master cabinet, must be reduced to 8;l
2
The two (24) relay cabinets must be configured from a
PC over USB as starting relay numbers 9 and 33;
3
The three (4) relay remotes, must be configured via the
control module dipswitch, for starting relay numbers 57,
61, & 65.
For instructions specific to your project, please contact our
Technical Services Department. The phone number can be found
on the back page of this manual.
Relay Numbering Chart
Leviton recommends that when planning your network, you fill
out the chart on the following page, or other similar chart which
you prefer to document your system. This completed chart
should be stored with your master relay panel complete with the
circuit schedules of all of the relay panels. For an example circuit
schedule, see page 41.