ZL0139-0A
Page 23 of 24
05145
Installation Guide
Power Monitoring
Series 4000-R
S4000-R
Register R/W NV Format
Units
Scale
Range
Description
277/278 R
Float
kW
Real Power, Phase B
279/280 R
Float
kW
Real Power, Phase C
281/282 R
Float
Ratio
0.0-1.0
Power Factor, Phase A
283/284 R
Float
Ratio
0.0-1.0
Power Factor, Phase B
285/286 R
Float
Ratio
0.0-1.0
Power Factor, Phase C
287/288 R
Float
Volt
Voltage, Phase A-B
289/290 R
Float
Volt
Voltage, Phase B-C
291/292 R
Float
Volt
Voltage, Phase A-C
293/294 R
Float
Volt
Voltage, Phase A-N
295/296 R
Float
Volt
Voltage, Phase B-N
297/298 R
Float
Volt
Voltage, Phase C-N
299/300 R
Float
Amp
Current, Instantaneous, Phase A
301/302 R
Float
Amp
Current, Instantaneous, Phase B
303/304 R
Float
Amp
Current, Instantaneous, Phase C
305/306 R
Float
Reserved, returns 0x7FC00000 (QNAN)
307/308 R
Float
Hz
45.0-65.0
Frequency (derived from Phase A)
309/310 R
NV Float
kVAh
Apparent Energy Consumption
311/312 R
NV Float
kVARh
Reactive Energy Consumption
313/314 R
Float
kVA
Apparent Power, Phase A
315/316 R
Float
kVA
Apparent Power, Phase B
317/318 R
Float
kVA
Apparent Power, Phase C
319/320 R
Float
kVAR
Reactive Power, Phase A
321/322 R
Float
kVAR
Reactive Power, Phase B
323/324 R
Float
kVAR
Reactive Power, Phase C
325/326 R
Float
kW
Total Real Power Present Demand
327/328 R
Float
kVAR
Total Reactive Power Present Demand
329/330 R
NV Float
kVA
Total Apparent Power Present Demand
331/332 R
NV Float
kW
Total Real Power Max Demand
333/334 R
NV Float
kVAR
Total Reactive Power Max Demand
335/336 R
NV Float
kVA
Total Apparent Power Max Demand
337/338* R
Float
0 -
4294967040 Pulse Counter 1 (Real Energy)
Contact Closure Counters. Valid for both Pulse
inputs and outputs. Counts are shown in (). See
register 144 (Energy per Pulse) for the Wh per
pulse count. Clear via register 129. Inputs are
user defined. These values are derived from the
32 bit integer counter and rolls over to 0 when
the integer counters do.
339/340* R
Float
0 -
4294967040
341/342* R
NV Float
kWh
Real Energy Consumption, Phase A
clear via reset register
343/344* R
NV Float
kWh
Real Energy Consumption, Phase B
345/346* R
NV Float
kWh
Real Energy Consumption, Phase C
Invalid or Quiet Not A Number (QNAN) conditions are indicated by 0x8000 (negative zero) for 16 bit integers and 0x7FC00000 for 32 bit floating point numbers.
Floating point numbers are encoded per the IEEE 754 32-bit specifications.
Modbus Point Map (cont.)
www.
.com
1.800.561.8187