background image

ZL0139-0A 

Page 21 of 24 

05145 

Installation Guide

Power Monitoring

Series 4000-R

Modbus Point Map (cont.)

S4000-R 

Register R/W NV Format

Units

Scale

Range

Description

138

R

SInt

-4  0.0001
-3  0.001
-2  0.01
-1  0.1
 0  1.0
 1  10.0
 2  100.0
 3  1000.0
 4  10000.0

Scale Factor I (Current)

Scale Factors

Note: These registers contain a signed integer, 

which scales the corresponding integer registers. 

Floating point registers are not scaled. Scaling 

is recalculated when the meter configuration is 

changed.

139

R

SInt

Scale Factor V (Voltage)

140

R

SInt

Scale Factor W (Power) 

141

R

SInt

Scale Factor E (Energy) 

142

R/W NV UInt

%

1-99

Phase Loss Voltage Threshold in percent of system voltage (register 

134). Default is 10 (%). Any phase (as configured in register 130) 

that drops below this threshold triggers a Phase Loss alert - i.e. 

if the System voltage is set to 480 V L-L, the L-N voltage for each 

phase should be 277 V. When the threshold is set to 10%, if any 

phase drops more than 10% below 277 V, (less than 249 V), or 

if any L-L voltage drops more than 10% below 480 V (less than 

432 V) the corresponding phase loss alarm bit in register 146 will 

be true.   

Phase Loss Output

Note: The phases tested are determined by the 

System Type.

143

R/W NV UInt

%

1-99

Phase Loss Imbalance Threshold in Percent. Default is 25% phase 

to phase difference. For a 3-phase Y (3 + N) system type (40 in 

register 130), both Line to Neutral and Line to Line voltages are 

tested. In a 3-phase Δ System type (31 in register 130), only Line 

to Line voltages are examined. In a single split-phase (2 + N) 

system type (12 in register 130), just the line to neutral voltage 

are compared. 

144

R/W NV UInt

Wh

10000, 
1000, 
100, 
10

Wh (& VARh, if equipped with 

FDS) Energy per Pulse Output 

Contact Closure.  If the meter 

cannot find a pulse duration 

that will keep up with the max. 

system power (register 135), 

it rejects the new value. Try a 

larger value.

kWh Pulse Contacts

Note: The kWh pulse contact can keep up with a maximum power (Watts) of 1800000 

x Wh pulse weight ÷ contact closure duration (in msec)

145

R

NV UInt

ms

500, 
250, 
100, 
50, 
25, 
10

Pulse Contact Closure Duration 

in msec. Read-only. Set to the 

slowest duration that keeps 

up with the theoretical max. 

system power (register 135). 

The open time  ≥ the closure 

time, so the max. pulse rate 

(pulses per sec) is the inverse of 

double the pulse time.

www.

.com

[email protected]

1.800.561.8187

Summary of Contents for 4000-R series

Page 1: ...tial failure modes of control paths and for certain critical control functions provide a means to acheive a safe state during and after a path failure Examples of critical control functions are emerge...

Page 2: ...0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 AWG 0 13 to 2 08 mm2 Rail T35 35mm DIN Rail per EN50022 OPERATING CONDITIONS Operating Temperature Range 30 to 70 C 22 to 158 F Storage Temperature Ra...

Page 3: ...g 8 Control Power 9 Quick Setup Instructions 10 Solid State Output 11 User Interface Menu Abbreviations Defined 11 User Interface for Data Configuration 12 Alert Reset Information 13 User Interface fo...

Page 4: ...ption FullDataSet FDS Power kW Energy kWh Configurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line L...

Page 5: ...s areclosed CONTROL POWER 0 1A 50 60 Hz A B C N 1 2 Alarm Energy NC NO S OUTPUT VA VB VC Neutral Earth Control Power UL 90V L N 600V L L CE 90V L N 300V L N VOLTAGE INPUTS CAT III 50 60 Hz X2 A X1 X2...

Page 6: ...ing by sliding them into the slots from the inside The stopping pegs must face the housing and the outside edge of the clip must be flush with the outside edge of the housing 2 Snap the clips onto the...

Page 7: ...Qty ID Type Modbus Register 130 User Interface SETUP S SYS VLL VLN Balance Diagram number Single PhaseWiring 2 1 A 2 A N L N 10 1L 1n AN 1 2 1 A 2 A B L L 11 2L AB 2 3 2 A B 3 A B N L L with N 12 2L 1...

Page 8: ...X2 X1 A B C N A B C N White Black White Black X1 X2 X1 X2 X1 X2 L1 L2 X2 X1 A B C N A B C White Black X1 X2 X1 X2 X1 X2 Diagram3 1 PhaseDirectVoltageConnection2CT L1 L2 L3 X2 X1 A B C N A B C X2 X1 X2...

Page 9: ...rce obey local and national code requirements For selecting fuses and circuit breakers use the following criteria Select current interrupt capacity based on the installation category and fault current...

Page 10: ...ough the digits Use the or buttons to select the CT size in amps b back to the S CT screen 7 to the S SYS Set System screen a to the SYSTM screen Use the or buttons to select the System Type see wirin...

Page 11: ...al Number RESET RESET Reset Data PASWD PASWD Enter Reset or Setup Password ENERG ENERG Reset Energy Accumulators DEMND DEMND Reset Demand Maximums User Interface UI Menu Abbreviations Defined The user...

Page 12: ...C VAC C KW C VLN A KVA B KVA C KVA A PF 3 PF B PF C PF 3KVAR Total Reactive Power Q AKVAR BKVAR CKVAR KVARh KVAh Accumulated Reactive Energy Qh Accumulated Apparent Energy Sh DEMND D KW Present Real P...

Page 13: ...ber Energy Pulse Output Error Overrun Error ConF Configuration Error PULSE Error ENERG rES Reset Energy Accumulators to 0 Unit Information Alert Status check if Wrench on LCD RESET Enter Reset Passwor...

Page 14: ...stalled See Install for wiring diagrams This value must be set before the System Voltage if used Potential Transformer RATIO 001 00 Back S V Back Sytem Voltage Next Set System Voltage V LL The nominal...

Page 15: ...nostic Alert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse When moving down to a smaller energy the meter will not allow the selection if it cannot find a pulse...

Page 16: ...S 485 transceivers are unit load or less RS 485 has a 47 k pull up to 5V and RS 485 has a 47 k pull down to Shield RS 485 signal ground Wire the RS 485 bus as a daisy chain from device to device witho...

Page 17: ...er interval 1 block mode 149 Demand sub interval length 900 sec 15 min 150 Modbus Address 001 Modbus Baud Rate 19200 baud Modbus Parity None Log Read Page 0 158 Logging Configuration Register 0 159 Lo...

Page 18: ...n Series 4000R Power Meter Full Data Set RESET SYSTEM RUNNING RSVersion x xxx last 2 bytes CRC 0x2B Read Device Identification BASIC implementation 0x00 0x01 and 0x02 data Conformity Level 1 Object va...

Page 19: ...C 019 R UInt Volt V 0 32767 Voltage Phase A N 020 R UInt Volt V 0 32767 Voltage Phase B N 021 R UInt Volt V 0 32767 Voltage Phase C N 022 R UInt Amp I 0 32767 Current Instantaneous Phase A 023 R UInt...

Page 20: ...31 40 Single Phase A N SystemType Single Phase A B Single Split Phase A B N 3 phase A B C no N 3 phaseY A B C N 131 R W NV UInt Amps 20 5000 CT Ratio Primary Current Inputs 132 R NV UInt n a Reserved...

Page 21: ...hase loss alarm bit in register 146 will be true Phase Loss Output Note The phases tested are determined by the SystemType 143 R W NV UInt 1 99 Phase Loss ImbalanceThreshold in Percent Default is 25 p...

Page 22: ...the number of sub intervals that make a single demand interval For block demand set this to 1 Demand Calculation 150 R W NV UInt Seconds 0 10 32767 Sub Interval Length in seconds For sync to comms se...

Page 23: ...t kVAR Reactive Power Phase A 321 322 R Float kVAR Reactive Power Phase B 323 324 R Float kVAR Reactive Power Phase C 325 326 R Float kW Total Real Power Present Demand 327 328 R Float kVAR Total Reac...

Page 24: ...perly Check all CTs and PTs to verify correct connection to the same service PT polarity and adequate powering See theWiring Diagrams section for more information Cannot communicate with power meter f...

Reviews: