background image

ZL0139-0A 

Page 14 of 24 

05145 

Installation Guide

Power Monitoring

Series 4000-R

UI for Setup

Next

Next

From:

 SETUP > PASWD

ADDR

--------

001

BAUD

--------

38400

19200

9600

4800

2400

1200

PAR

--------

nOnE

EvEn

Odd

Set Communications Parameters:

ADDR - Modbus Address: 

1 – 247. 

+

increments the selected (blinking) digit.

-

selects the digit to the left.

BAUD - Baud Rate: 

1200 – 38400 Baud

PAR - Parity: 

Odd, Even, None

+

or

to step through the options.

Set Current Transducer:

CT SZ -

CT Size: in Amps. Maximum is 5000 Amps.

Set System Configuration: 

SYSTM:   +

or

to step through the following System Type options:

System Reg 130 CTs Description

3L-1n

40

3        Wye Three Phase: A,  B, & C with Neutral (Default).

3L

31

3        Delta Three Phase: A, B & C; no Neutral

2L-1n

12

2        Single Split Phase: A & B with Neutral

2L

11

1        Single Phase: A & B; no Neutral

1L-1n

10

1        Single Phase: A to Neutral

System 

Type

Current 

Transformer

S  SYS

Next

S  CT

CT SZ

--------

100

SYSTM

--------

3L-1n

  3L

  2L-1n

  2L

  1L-1n

Bac

To

 SETU

P

Back

Back

Back

S COM

To Setup p. 2 “SPLOS”

Next

S  PT

Set Potential Transfomer Ratio: 

RATIO –

 Potential transformer step down is RATIO:1. Default is 1:1 

(No PT installed). See Install for wiring diagrams. This value must be 

set before the System Voltage (if used).

Potential

Transformer

RATIO

--------

001.00

Back

S     V

Back

Sytem

Voltage

Next

Set System Voltage:

V LL –

The nominal Line to Line Voltage for the system. This is used 

by the meter to calculate the theoretical maximum system power, and 

as the reference voltage for setting the Phase Loss threshold. 

Maximum is 32000 Volts. For system type 1+N (10), this is a Line to 

Neutral Voltage, indicated by “V LN”. Note: the meter will reject settings 

that are not within the meter’s operating range when divided by the PT 

ratio. 

  V LL

--------

00600

S  PWR

Back

Sytem

Voltage

MX  KW 

--------

103.92

Next

System Power:

MX KW –

The theoretical Maximum System Power is calculated by the 

meter from the System Voltage, CT size, and System Type. Power 

Factor is assumed to be unity. The value of System Power is used to  

determine which combinations of pulse weight and duration are valid 

and will keep up with the maximum power the meter will see. This value 

is read only. 

Note: 

Bold 

is the Default.

To Setup p. 2 “SPASS”

RS-485

Output 

† When leaving this parameter screen using the right button (  ), the display will 
briefly indicate “SAvEd)” to confirm that any changes made have been accepted.

www.

.com

[email protected]

1.800.561.8187

Summary of Contents for 4000-R series

Page 1: ...tial failure modes of control paths and for certain critical control functions provide a means to acheive a safe state during and after a path failure Examples of critical control functions are emerge...

Page 2: ...0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 AWG 0 13 to 2 08 mm2 Rail T35 35mm DIN Rail per EN50022 OPERATING CONDITIONS Operating Temperature Range 30 to 70 C 22 to 158 F Storage Temperature Ra...

Page 3: ...g 8 Control Power 9 Quick Setup Instructions 10 Solid State Output 11 User Interface Menu Abbreviations Defined 11 User Interface for Data Configuration 12 Alert Reset Information 13 User Interface fo...

Page 4: ...ption FullDataSet FDS Power kW Energy kWh Configurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line L...

Page 5: ...s areclosed CONTROL POWER 0 1A 50 60 Hz A B C N 1 2 Alarm Energy NC NO S OUTPUT VA VB VC Neutral Earth Control Power UL 90V L N 600V L L CE 90V L N 300V L N VOLTAGE INPUTS CAT III 50 60 Hz X2 A X1 X2...

Page 6: ...ing by sliding them into the slots from the inside The stopping pegs must face the housing and the outside edge of the clip must be flush with the outside edge of the housing 2 Snap the clips onto the...

Page 7: ...Qty ID Type Modbus Register 130 User Interface SETUP S SYS VLL VLN Balance Diagram number Single PhaseWiring 2 1 A 2 A N L N 10 1L 1n AN 1 2 1 A 2 A B L L 11 2L AB 2 3 2 A B 3 A B N L L with N 12 2L 1...

Page 8: ...X2 X1 A B C N A B C N White Black White Black X1 X2 X1 X2 X1 X2 L1 L2 X2 X1 A B C N A B C White Black X1 X2 X1 X2 X1 X2 Diagram3 1 PhaseDirectVoltageConnection2CT L1 L2 L3 X2 X1 A B C N A B C X2 X1 X2...

Page 9: ...rce obey local and national code requirements For selecting fuses and circuit breakers use the following criteria Select current interrupt capacity based on the installation category and fault current...

Page 10: ...ough the digits Use the or buttons to select the CT size in amps b back to the S CT screen 7 to the S SYS Set System screen a to the SYSTM screen Use the or buttons to select the System Type see wirin...

Page 11: ...al Number RESET RESET Reset Data PASWD PASWD Enter Reset or Setup Password ENERG ENERG Reset Energy Accumulators DEMND DEMND Reset Demand Maximums User Interface UI Menu Abbreviations Defined The user...

Page 12: ...C VAC C KW C VLN A KVA B KVA C KVA A PF 3 PF B PF C PF 3KVAR Total Reactive Power Q AKVAR BKVAR CKVAR KVARh KVAh Accumulated Reactive Energy Qh Accumulated Apparent Energy Sh DEMND D KW Present Real P...

Page 13: ...ber Energy Pulse Output Error Overrun Error ConF Configuration Error PULSE Error ENERG rES Reset Energy Accumulators to 0 Unit Information Alert Status check if Wrench on LCD RESET Enter Reset Passwor...

Page 14: ...stalled See Install for wiring diagrams This value must be set before the System Voltage if used Potential Transformer RATIO 001 00 Back S V Back Sytem Voltage Next Set System Voltage V LL The nominal...

Page 15: ...nostic Alert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse When moving down to a smaller energy the meter will not allow the selection if it cannot find a pulse...

Page 16: ...S 485 transceivers are unit load or less RS 485 has a 47 k pull up to 5V and RS 485 has a 47 k pull down to Shield RS 485 signal ground Wire the RS 485 bus as a daisy chain from device to device witho...

Page 17: ...er interval 1 block mode 149 Demand sub interval length 900 sec 15 min 150 Modbus Address 001 Modbus Baud Rate 19200 baud Modbus Parity None Log Read Page 0 158 Logging Configuration Register 0 159 Lo...

Page 18: ...n Series 4000R Power Meter Full Data Set RESET SYSTEM RUNNING RSVersion x xxx last 2 bytes CRC 0x2B Read Device Identification BASIC implementation 0x00 0x01 and 0x02 data Conformity Level 1 Object va...

Page 19: ...C 019 R UInt Volt V 0 32767 Voltage Phase A N 020 R UInt Volt V 0 32767 Voltage Phase B N 021 R UInt Volt V 0 32767 Voltage Phase C N 022 R UInt Amp I 0 32767 Current Instantaneous Phase A 023 R UInt...

Page 20: ...31 40 Single Phase A N SystemType Single Phase A B Single Split Phase A B N 3 phase A B C no N 3 phaseY A B C N 131 R W NV UInt Amps 20 5000 CT Ratio Primary Current Inputs 132 R NV UInt n a Reserved...

Page 21: ...hase loss alarm bit in register 146 will be true Phase Loss Output Note The phases tested are determined by the SystemType 143 R W NV UInt 1 99 Phase Loss ImbalanceThreshold in Percent Default is 25 p...

Page 22: ...the number of sub intervals that make a single demand interval For block demand set this to 1 Demand Calculation 150 R W NV UInt Seconds 0 10 32767 Sub Interval Length in seconds For sync to comms se...

Page 23: ...t kVAR Reactive Power Phase A 321 322 R Float kVAR Reactive Power Phase B 323 324 R Float kVAR Reactive Power Phase C 325 326 R Float kW Total Real Power Present Demand 327 328 R Float kVAR Total Reac...

Page 24: ...perly Check all CTs and PTs to verify correct connection to the same service PT polarity and adequate powering See theWiring Diagrams section for more information Cannot communicate with power meter f...

Reviews: