Installation Guide

Power Monitoring

Series 4000-R

Problem

Cause

Solution

The maintenance wrench icon appears 

in the power meter display.

There is a problem with the inputs 

to the power meter.

See the Alert sub-menu or the Diagnostic Alert Modbus 

Register 146

The display is blank after applying 

control power to the meter.

The meter is not receiving adequate 

power.

Verify that the meter control power are receiving the required 

voltage. 

Verify that the heart icon is blinking.
Check the fuse.

The data displayed is inaccurate.

Incorrect setup values

Verify the values entered for power meter setup parameters 

(CT and PT ratings, system type, etc.). See the Setup section.

Incorrect voltage inputs

Check power meter voltage input terminals to verify 

adequate voltage.

Power meter is wired improperly.

Check all CTs and PTs to verify correct connection to the same 

service, PT polarity, and adequate powering. See the Wiring 

Diagrams section for more information.

Cannot communicate with power meter 

from a remote personal computer.

Power meter address is incorrect.

Verify that the meter is correctly addressed (see Setup 

section).

Power meter baud rate is incorrect.

Verify that the baud rate of the meter matches that of 

all other devices on its communications link (see Setup 

section).

Communications lines are 

improperly connected.

Verify the power meter communications connections (see the 

Communications section).

Verify the terminating resistors are properly installed on 

both ends of a chain of units. Units in the middle of a chain 

should not have a terminator.

Verify the shield ground is connected between all units.

Troubleshooting

China RoHS Compliance Information 
(EFUP Table)

部件名称 

产品中有毒有害物质或元素的名称及含量Substances

铅 (Pb) 汞 (Hg)

镉 (Cd)

六价铬 (Cr(VI))

多溴联苯(PBB)

多溴二苯醚(PBDE)

电子线路板 

X

O

O

O

O

O

O = 表示该有毒有害物质在该部件所有均质材料中的含量均在 SJ/T11363-2006 标准规定的限量要求以下.

X = 表示该有毒有害物质至少在该部件的某一均质材料中的含量超出SJ/T11363-2006标准规定的限量要求.

Z000057-0A

www.

.com

[email protected]

1.800.561.8187

Summary of Contents for 4000-R series

Page 1: ...tial failure modes of control paths and for certain critical control functions provide a means to acheive a safe state during and after a path failure Examples of critical control functions are emerge...

Page 2: ...0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 AWG 0 13 to 2 08 mm2 Rail T35 35mm DIN Rail per EN50022 OPERATING CONDITIONS Operating Temperature Range 30 to 70 C 22 to 158 F Storage Temperature Ra...

Page 3: ...g 8 Control Power 9 Quick Setup Instructions 10 Solid State Output 11 User Interface Menu Abbreviations Defined 11 User Interface for Data Configuration 12 Alert Reset Information 13 User Interface fo...

Page 4: ...ption FullDataSet FDS Power kW Energy kWh Configurable for CT PT ratios system type and passwords Diagnostic alerts Current 3 phase average Volts 3 phase average Current by phase Volts by phase Line L...

Page 5: ...s areclosed CONTROL POWER 0 1A 50 60 Hz A B C N 1 2 Alarm Energy NC NO S OUTPUT VA VB VC Neutral Earth Control Power UL 90V L N 600V L L CE 90V L N 300V L N VOLTAGE INPUTS CAT III 50 60 Hz X2 A X1 X2...

Page 6: ...ing by sliding them into the slots from the inside The stopping pegs must face the housing and the outside edge of the clip must be flush with the outside edge of the housing 2 Snap the clips onto the...

Page 7: ...Qty ID Type Modbus Register 130 User Interface SETUP S SYS VLL VLN Balance Diagram number Single PhaseWiring 2 1 A 2 A N L N 10 1L 1n AN 1 2 1 A 2 A B L L 11 2L AB 2 3 2 A B 3 A B N L L with N 12 2L 1...

Page 8: ...X2 X1 A B C N A B C N White Black White Black X1 X2 X1 X2 X1 X2 L1 L2 X2 X1 A B C N A B C White Black X1 X2 X1 X2 X1 X2 Diagram3 1 PhaseDirectVoltageConnection2CT L1 L2 L3 X2 X1 A B C N A B C X2 X1 X2...

Page 9: ...rce obey local and national code requirements For selecting fuses and circuit breakers use the following criteria Select current interrupt capacity based on the installation category and fault current...

Page 10: ...ough the digits Use the or buttons to select the CT size in amps b back to the S CT screen 7 to the S SYS Set System screen a to the SYSTM screen Use the or buttons to select the System Type see wirin...

Page 11: ...al Number RESET RESET Reset Data PASWD PASWD Enter Reset or Setup Password ENERG ENERG Reset Energy Accumulators DEMND DEMND Reset Demand Maximums User Interface UI Menu Abbreviations Defined The user...

Page 12: ...C VAC C KW C VLN A KVA B KVA C KVA A PF 3 PF B PF C PF 3KVAR Total Reactive Power Q AKVAR BKVAR CKVAR KVARh KVAh Accumulated Reactive Energy Qh Accumulated Apparent Energy Sh DEMND D KW Present Real P...

Page 13: ...ber Energy Pulse Output Error Overrun Error ConF Configuration Error PULSE Error ENERG rES Reset Energy Accumulators to 0 Unit Information Alert Status check if Wrench on LCD RESET Enter Reset Passwor...

Page 14: ...stalled See Install for wiring diagrams This value must be set before the System Voltage if used Potential Transformer RATIO 001 00 Back S V Back Sytem Voltage Next Set System Voltage V LL The nominal...

Page 15: ...nostic Alert Bitmap if equipped Wh P Set Pulse Energy In Watt Hours VAR Hours if present per Pulse When moving down to a smaller energy the meter will not allow the selection if it cannot find a pulse...

Page 16: ...S 485 transceivers are unit load or less RS 485 has a 47 k pull up to 5V and RS 485 has a 47 k pull down to Shield RS 485 signal ground Wire the RS 485 bus as a daisy chain from device to device witho...

Page 17: ...er interval 1 block mode 149 Demand sub interval length 900 sec 15 min 150 Modbus Address 001 Modbus Baud Rate 19200 baud Modbus Parity None Log Read Page 0 158 Logging Configuration Register 0 159 Lo...

Page 18: ...n Series 4000R Power Meter Full Data Set RESET SYSTEM RUNNING RSVersion x xxx last 2 bytes CRC 0x2B Read Device Identification BASIC implementation 0x00 0x01 and 0x02 data Conformity Level 1 Object va...

Page 19: ...C 019 R UInt Volt V 0 32767 Voltage Phase A N 020 R UInt Volt V 0 32767 Voltage Phase B N 021 R UInt Volt V 0 32767 Voltage Phase C N 022 R UInt Amp I 0 32767 Current Instantaneous Phase A 023 R UInt...

Page 20: ...31 40 Single Phase A N SystemType Single Phase A B Single Split Phase A B N 3 phase A B C no N 3 phaseY A B C N 131 R W NV UInt Amps 20 5000 CT Ratio Primary Current Inputs 132 R NV UInt n a Reserved...

Page 21: ...hase loss alarm bit in register 146 will be true Phase Loss Output Note The phases tested are determined by the SystemType 143 R W NV UInt 1 99 Phase Loss ImbalanceThreshold in Percent Default is 25 p...

Page 22: ...the number of sub intervals that make a single demand interval For block demand set this to 1 Demand Calculation 150 R W NV UInt Seconds 0 10 32767 Sub Interval Length in seconds For sync to comms se...

Page 23: ...t kVAR Reactive Power Phase A 321 322 R Float kVAR Reactive Power Phase B 323 324 R Float kVAR Reactive Power Phase C 325 326 R Float kW Total Real Power Present Demand 327 328 R Float kVAR Total Reac...

Page 24: ...perly Check all CTs and PTs to verify correct connection to the same service PT polarity and adequate powering See theWiring Diagrams section for more information Cannot communicate with power meter f...

Reviews: