Configuration / device parameters
Leuze electronic GmbH + Co. KG
BPS 8
54
8.5.2 Position detection
Figure 8.6: Position detection tab
Description:
The position detection controls all settings that affect the position values.
Resolution parameter
With the Resolution parameter, the resolution for the position values is defined. This parameter also
performs a rounding correction (the position value is divided by the defined value range).
Parameter
Description
Value range
Default
Unit
CR
Resolution in
[mm]
The parameter specifies
the resolution for the
position value. The reso
-
lution has no effect on
- Static preset
- Offset.
1: 0.01
2: 0.1
3: 1
4: 10
5: 100
6: 1,000
3
mm
–
NOTE
The resolution only determines the mathematical decimal value and has no effect on the
measurement accuracy.
NOTE
Maximum position value which can be represented
The binary protocols 1 to 6 convey the position value with a different number of data bits. The
number of data bits and the selected resolution determine the maximum position value that
can be represented.
a
Maximum position value which can be represented with a resolution of
1mm (default)
0.1mm
0.01mm
0.001mm
Binary protocol 1, 4, 6
(32 data bits)
10,000,000 mm
a)
10,000,000mm
1)
10,000,000mm
1)
4,294,967mm
Binary protocol 2
(24 data bits)
10,000,000mm
1)
1,677,721mm
167,772mm
16,777mm
Binary protocol 3
(21 data bits)
2,097,152mm
209,715mm
20,971mm
2,097mm