Communicating with the Device
Leuze
electronic
82
BCL 40
Leuze electronic
Copy parameter set
Notice!
A valid parameter set operation must be acknowledged with ’PS0’. Should an error occur,
the command should be repeated. Repeated error acknowledgements indicate an error in
the parameter set. If in doubt, contact your Leuze sales or service office (see back page for
addresses).
Command
’PC’
Description
Copies the given source parameter set into the given target parameter set
Parameter
BCL 40 Stand alone:
’0’ Current parameter set.
’2’ parameter set with factory default settings.
Example
’PC20’: Reset to factory default settings
BCL 40 with MA 10:
’0’ Current parameter set.
’1’ customer-specific parameter set.
’2’ parameter set with factory default settings.
Example
’PC20’: Reset to factory default settings
’PC01’: The current parameter set is copied in the customer-specific
parameter set (backup)
’PC10’: Reset to customer-specific settings
Acknowledge-
ment
’PSx’
x:
Status
'0' valid parameter set
'1' invalid message
'2' invalid message length
'3' invalid block check type
'4' invalid block check checksum
'5' invalid data length
'6' invalid message data
'7' invalid start address
'8' invalid parameter set
'9' invalid parameter type