Electrical connection
Leuze electronic
OGS 600
20
TNT
35/7-2
4
V
5.2
Voltage supply
The OGS 600 guidance sensors are designed for a voltage supply of 18 … 30VDC (PELV
– protective extra low voltage with reliable disconnection). The current consumption with
24 V DC is approx. 180 mA.
5.2.1
Shielding
NOTE
Shielded connection cables!
Only shielded connection cables should be used; they ensure that the housing of the
OGS 600 is connected to functional earth.
Use only shielded connection cables!
The shielding must be connected to earth potential on the connection side.
If unshielded connection cables are used, a separate cable must be routed from the
housing to the earth potential (additional earthing screw on the housing cover and in
the fastening groove).