Starting up the device
Leuze electronic
ODS 9
35
Configuring switching point modes
The following switching point modes can also be configured. These are structured according to the switch-
ing profiles of the
Smart Sensor Profile
specification.
• SinglePoint Object mode (SinglePt Obj): single switching point taught on an object
• Window: window mode
• TwoPoint: two-point mode
• SinglePoint Background mode (SinglePt BG): single switching point taught against a background
SinglePoint Object mode (SinglePt Obj)
When teaching setpoint SP1 before of after, the object (Obj) is targeted, i.e., with SP1, the SSC is still ac-
tive. The SSC becomes inactive only after SP1.
1
3
2
3
4
5
6
1
1
Setpoint SP1
2
Measurement range minimum
3
Hysteresis
4
Signal response
5
Sensor/SSC
6
Reserve if >0
Fig. 7.3:
SinglePoint Object switching point mode
• Only setpoint SP1 (not SP2) is used for calculating the switching edges. The lower switching edges are
always at the lower limit value.
• Reserve and hysteresis run from the upper switching point into the distance, so that the switching out-
put has reliably (i.e., with reserve) switched on after the teach event (provided it is light switching
high
active
).