Commissioning and configuration
Leuze electronic
MA 258
i
73
TNT
35/7-2
4
V
Attention!
If the configuration assembly is addressed with instance 118 and length 12 in the input mask
for the generic module, all MA 258
i
parameters with the value 0 are occupied in the first
moment. All default parameters of the MA must be manually entered in the configuration
assembly. Changing the individual default values is possible at any time.
For the exact description of the assemblies for input/output and configuration, please refer
to chapter 12.6.2.
The query cycle of the input and output assemblies is subsequently defined in the
Module
properties
->
Connection
path in the
Request packet interval (RPI)
input field.
The participant is thereby defined in offline mode; the data must subsequently be transferred
to the control.
12.3.2
Configure the config assembly
The MA 258
i
makes available a configuration assembly that allows the entire parameter set
of the MA 258
i
to be saved in the control and, if necessary, to be called up.
The config assembly must include all parameters that affect the MA 258
i
. The config
assembly is automatically written to the connected participants in cycles that the control
manufacturer defines.
The config assembly is implemented in class 4, under instance 118. By default, all param-
eters are preset to the value 0 (zero).
Attention!
If the config assembly is not adapted, the MA 258
i
displays a corresponding behavior acc.
to the parameters preset with 0.
Switch the control to offline mode.
Double-click
Controller tags
to edit the configuration assembly.
The configuration assembly can be recognized by the index "C" appended to the device
name.
Parameter entry is performed as described in section "Setting MA parameters manually via
the config assembly" on page 74.