background image

WARNING 

- Electrical power must be supplied

through an external circuit breaker or fuse protection.
An external switch must be provided to turn off
power. Always turn off power before removing the
internal field wiring panel.

Pneumatic connections:

Connect air supply and output lines to the 1/8” NPT
connections at the bottom of the controller The center
connection is for air exhaust and is supplied with a porous
metal filter/silencer which should not be removed.

Corrosion resistant 3/8 in. O.D. tubing or 1/4 in. pipe is
recommended for the air lines. Connect air supply to the
right hand connection labeled “Input” and output to left
hand connection labeled “Output” to actuator. See Figure 1.
The supply line should be fitted with a pressure gauge and 50
micron filter/regulator to remove any floating particles. If the
supply air is mixed with traces of oil, a filter capable of
removing oil should be used. (CAUTION: Some lubricating
oils permanently damage solenoid valves.)

W A R N I N G  

- Turn off electrical power before

removing the internal field wiring panel

Field Wiring: 

1.

After mounting the PMC-1 at the desired location, open
the cover by loosening 5 screws and the thumb screw.
Then remove the field wiring panel by loosening two
captive screws. The terminal block wiring diagram
shown in Figure 2 appears on the back of the panel.
Power and signal lines should be routed through
separate conduits to avoid interference. Transmitter or
RTD signal lines should use shielded cable grounded at
terminal 2 in insure against RF interference.

2.

Connect the transmitter wires as shown in Figure 3 . A
two wire transmitter should be powered with the 24v DC
supply from the PMC-1 by connecting the positive wire
to terminal number 1 and the other transmitter wire to
terminal 3 of TB-2. Twisted pair wires can be used for
connecting the transmitter to the PMC-1. If a shielded
pair of wires is used,connect the shield to terminal 2 of
TB-2. Jumper at J5/J6 must be on J5. For 4-wire
transmitters,see Appendix B.

3.

For external set point connection (4-20mA) connect two
wires to terminals 5 and 4 of TB-2. Terminal 5 is positive
(current flows into terminal 5) and terminal 4 is
negative. (See Figure 4)

A. Introduction                                     

The Leslie PMC-1 electro-pneumatic controller can be used
to control pressure, temperature. liquid level, and other
process variables. It accepts signals from any standard 4-20
mA transmitter and provides a pneumatic output to operate a
diaphragm control valve, etc. It provides the following
features:

1)

The controller supplies 24 volt D C. power for the
transmitter, eliminating the need for a separate D.C.
power supply.

2)

It provides high volume air output at pressures up to 100
psig to directly operate a diaphragm control valve. I/P
transducers and valve positioners are not required or
recommended.

3)

There are no small air orifices to plug or foul (.060” dia.
solenoid ports)

4)

There is no air consumption except when air is being
loaded onto the control valve diaphragm.

B. Operation

The electronic circuit of the controller compares the signal
from the transmitter to the desired set point. If the error is
greater than the dead band, electrical pulses are sent to one
of the two internal air solenoid valves. One valve increases
output air pressure and the other bleeds it. Each time a pulse
is received, the resulting pressure on the diaphragm of the
control valve increases or decreases slightly. If the error is
large, the solenoid valves are held open longer to increase the
speed of output changes. For small errors, the pulse width is
decreased to prevent overshoot. The response speed
adjustment can be used to control how quickly the output
changes for a given error. Adjusting the dead band will allow
the controller to ignore small changes or “noise” in the
system. The overall result is a more accurate and stable
system.

C. Installation

Mount the controller in a location that will allow access to
the internal adjustments. See Figure 1 for mounting
dimensions. It should be mounted in a location where the
temperature will be between -4°F and 140°F. Temperatures
above or below these limits will affect the LCD although the
controller would continue to function. A location within 50
ft. of the control valve is recommended to reduce time lags in
the pneumatic signal. Where the distance to the control valve
is large, an optional external solenoid valve package (PMC-1
local control module model RCS-90) can be used.

FIGURE 2

4

Summary of Contents for PMC-1

Page 1: ...AND MAINTENANCE INSTRUCTIONS DIAGRAMS PARTS LIST 12501 Telecom Drive Tampa FL 33637 PMC 1 ELECTRO PNEUMATIC CONTROLLER T A B L E O F C O N T E N T S Specifications 2 Introduction 4 Operation 4 Installation 4 Pneumatic Connections 4 Field Wiring 4 Start Up 5 Troubleshooting 6 ...

Page 2: ...TION NO AIR CONSUMPTION AT STEADY STATE DISPLAY 3 1 2 DIGIT LCD BACKLIT DISPLAY GREEN BACKGROUND ACCURACY 0 5 OF FULL SPAN SETTING ACCURACY ACTUAL SET VALUE COINCIDES WITH INDICATED SET VALUE RESPONSE SPEED RANGE 200 1 AMPLIFIER GAIN SLOW LOOP NORMAL 6 MAX HIGH 12 MAX DEAD BAND ADJUSTABLE FROM 0 TO 5 OF FULL SPAN INPUT RESISTANCE TO CURRENT LOOP 100 OHMS X CURRENT 0 7 VOLTS AMBIENT TEMPERATURE 4 F...

Page 3: ...3 PMC CONTROLLER MOUNTING DIMENSIONS INCHES MM A C Power Electrical Signal Input Output Pneumatic Input 100 psi Max Vent Pneumatic Output FIGURE 1 ...

Page 4: ...current flows into terminal 5 and terminal 4 is negative See Figure 4 A Introduction The Leslie PMC 1 electro pneumatic controller can be used to control pressure temperature liquid level and other process variables It accepts signals from any standard 4 20 mA transmitter and provides a pneumatic output to operate a diaphragm control valve etc It provides the following features 1 The controller su...

Page 5: ...remote location from a control valve 6 When the PMC 1 is being used as a temperature controller with an RTD an optional signal conditioning card calibrated for a temperature range suitable for the process must be installed in TB 5 Jumper at J5 J6 must be on J6 See figure 7 For a 3 wire RTD connect the two RTD wires that are internally connected together zero resistance between them to terminals 16...

Page 6: ...ated to read 25 0 when the CALIBRATE LO LED is lit and 175 0 when the CALIBRATE Hl LED is lit J7 0 000 to 1 999 J8 00 00 to 19 99 J9 000 0 to 199 9 J10 0000 to 1999 10 Using one of the pressure sensitive labels supplied label the display to indicate the unit of measurement for your process i e pressure temperature gpm etc 11 Adjust the air supply pressure to the controller by adjusting the filter ...

Page 7: ...lack Red TB 2 Approximate resistance 0 Ω Approximate resistance 75 F 109 Ω Unused terminal not connected 3 Wire RTD Head Wiring Connections for Two Wire RTD temperature Jump Black RTD lead Red RTD lead Terminal colored red or other contrasting color NOTE Jumper J5 J6 must be on J6 ...

Page 8: ... cable that the shielding is connected to the earth ground 4 Insufficient air pressure to PMC 1 a Make sure that the air pressure supplied to the PMC 1 is sufficient to fully stroke the control valve or to provide the maximum outlet pressure required from a regulator 5 Leaks in pneumatic lines a Small pneumatic line leaks can cause control instability particularly when using the PMC 1 with a regul...

Page 9: ...ED AND EXTERNAL POWER CAN BE BROUGHT TO THE SOLENOIDS AT TB 2 PIN 14 J5 JUMP WHEN EXTERNAL 4 20MA PROCESS FEEDBACK TRANSMITTER IS USED OR J6 JUMP WHEN RTD SIGNAL CONDITONAL CARD IS INDSTALLED IN THE PMC 1 J7 DECIMAL POINT SELECT REFER TO SECTION D PARA 7 J8 DECIMAL POINT SELECT REFER TO SECTION D PARA 7 J9 DECIMAL POINT SELECT REFER TO SECTION D PARA 7 J10 DECIMAL POINT SELECT REFER TO SECTION D P...

Page 10: ... Resistance x Current Voltage 100 x 020 0 7 Voltage 2 7 Volts Thus at 20mA the voltage drop of the PMC s transmitter loop is 2 7 volts EXAMPLE The PMC 1 is being used in a level control application The differential pressure transmitter used to measure the level has a minimum power requirement of 12 volts A chart recorder with an impedance resistance of 450Ω is being considered for use with the lev...

Page 11: ...l 3 receives the 4 20mA signal back 11 Terminal 2 is an earth ground A 4 wire transmitter needs two additional wires because it receives its power from a separate power source This type of transmitter can also be used with the PMC 1 and it is connected as shown in Figure 9 Since it receives its power from a separate source terminal 1 the PMC 1 s power is not used The 4 20mA signal from the transmi...

Page 12: ...alled in the PMC 1 is a variable voltage signal The signal conditioning card converts the voltage signal into a 4 20mA signal which can be used by the PMC 1 The wire connecting the RTD to the PMC 1 provides additional resistance which varies according to the gauge and length of the wire Although the additional resistance of the wire is insignificant over short distances it can affect accuracy over...

Page 13: ... cases the arrangement shown above is recommended A standard three way solenoid valve is installed in the air line between the PMC 1 and the control valve The solenoid is energized from the same power source used by the PMC 1 When the solenoid is energized ports B and C are connected and the pneumatic circuit between the PMC 1 and control valve is complete On loss of power the solenoid is no longe...

Page 14: ...oning card to the set point and using a series of short pneumatic pulses modulates the control valve as required to maintain the set point The PMC 1 s slow loop control mode can be selected for enhanced control in systems that respond slowly to control valve changes During installation the PMC 1 is calibrated by dialing in the upper and lower limits of the signal conditioning card The set point an...

Page 15: ...solating valve The isolating valve provides the ability to change or calibrate the pressure transmitter without otherwise disturbing the system The pig tail is important in steam applications to avoid overheating the pressure transmitter The loop in the pig tail maintains a condensate buffer between the steam and the sensing diaphragm of the pressure transmitter During installation the PMC 1 is ca...

Page 16: ...ine measures the static pressure in the system and acts as a reference point the difference between the upper and lower sensing lines is the head pressure of the liquid In an open system the reference line is vented to atmosphere A three valve manifold is recommended for use with the dp transmitter to facilitate isolation of the transmitter for replacement or in line calibration During installatio...

Reviews: