background image

8

2)

Control valve operates in the opposite direction required
to satisfy the system .
a) Check position of direct/reverse switch.

3)

Controller does not operate at all (LCD display off).
a) Check A.C. power connection.
b) Check fuse (F1 in Figure 2).
c) PMC-1 operates but no display, replace LCD display.

4)

Controller does not respond to changes in local set point
adjustment.
a) Check that the set point jumper is in the local

position.

5)

Controller does not respond to changes in the controlled
variable.
a) Check connections and signal from transmitter.
b) Re-check LO-HI calibration and set point.

6)

The displayed process value does not match the actual
when measured against thermometer or pressure gauge.
a) Check display calibration (step 9 of start-up

instructions). 

b) Check calibration of transmitter. (See instructions

supplied with transmitter).

c) Remember, the accuracy of the PMC-1 is ±.5% of span

(much better than most gauges or thermometers).
For example, if calibration was from 32-212°F, the
span is 180° so the indicated temperature of the PMC-
1 would be within (.005 x 180) .9°F of actual.

7)

Control valve does not respond to controller output.
a) Check filter/regulator supplying air to controller to

make sure that the output pressure is 5-10 psig higher
than the pressure required to fully stroke the valve.

b) Check actuator operation.

8)

Process never quite makes the set point.
a) Check pneumatic connections for leaks.

For Temperature Control Systems

1)

RTD connection to PMC-1
a) If an RTD is being used, make sure that the wires are

connected according to the diagram in the PMC-1
Installation and Operation Manual. If in doubt,
measure the resistance across the terminals, as shown
in Figure 5.

2)

RTD installation in piping
a) If the process temperature indicated by the PMC-1 (a

function of the RTD signal) lags considerably behind a
thermometer installed in the process line, check to
make sure that the RTD is installed directly into the
flow path of the process fluid. Unless absolutely
necessary, the RTD should not be inside a thermowell.
If the above steps have been taken and the lag is still
too great, thermocouple with transmitter may be
necessary.

3)

RF interference
a) For best protection from radio frequency interference.

make sure that the temperature sensing element is
connected to the PMC-1 using shielded cable that the
shielding is connected to the earth ground.

4)

Insufficient air pressure to PMC-1
a) Make sure that the air pressure supplied to the PMC-1

is sufficient to fully stroke the control valve or to

provide the maximum outlet pressure required from a
regulator.

5)

Leaks in pneumatic lines
a) Small pneumatic line leaks can cause control

instability, particularly when using the PMC-1 with a
regulator. Use a soap solution or “snoop” to locate
possible leaks.

6)

Too much air pressure to PMC-1
a) If too much air pressure is supplied to the PMC-1, it

can overload the actuator or regulator diaphragm
causing overshoot and slow response when venting is
required.

7)

Inaccurate calibration
a) If the process temperature indicated by the PMC-1 is

significantly different from the temperature indicated
by a thermometer, check to make sure that the PMC-
1 is calibrated according to the range of the signal
conditioning card installed (if using an RTD) or the
range of the temperature transmitter (if using a
thermocouple).

8)

Trapping problems
a) A steam trap that is under sized or malfunctioning

can cause the heat exchanger to flood during high
load conditions, giving rise to wide swings in process
temperature. Check for this problem by manually
bypassing the trap under full load conditions, and
observe whether there is an improvement in
temperature control.

9)

Incorrect Installation of Regulator
a) A poorly installed regulator can cause cycling. Make

sure  that the regulator is installed in the proper
orientation and that the sensing line is installed to
provide proper condensate drainage, as indicated in
the regulator’s Installation and Operation Manual.

10) Poor performance or malfunction of control valve

a) A malfunctioning control valve component, such as a

leaking or broken actuator stem seal, can cause the
system to work poorly or not at all. Also, if an existing
control valve from another manufacturer has been
used in the system, check for hysteresis, ability to
throttle properly, and sizing (over or under).

10 Most Common Problems

1 ) Leaky air connections - must be tested bubble tight with

soapy water solution.

2)

Incorrect field wiring. Re-check connections in reverse

order of how they were connected.

3)

Loose connections.

4)

Incorrect calibration.

5)

Speed of response and dead band adjustment.

6)

Insufficient air pressure supply.

7)

LCD decimal selector in wrong position.

8)

Oversized or malfunctioning control valve/regulator.

9)

Poor condensate drainage from heat exchangers.

10) Wrong supply voltage.

Summary of Contents for PMC-1

Page 1: ...AND MAINTENANCE INSTRUCTIONS DIAGRAMS PARTS LIST 12501 Telecom Drive Tampa FL 33637 PMC 1 ELECTRO PNEUMATIC CONTROLLER T A B L E O F C O N T E N T S Specifications 2 Introduction 4 Operation 4 Installation 4 Pneumatic Connections 4 Field Wiring 4 Start Up 5 Troubleshooting 6 ...

Page 2: ...TION NO AIR CONSUMPTION AT STEADY STATE DISPLAY 3 1 2 DIGIT LCD BACKLIT DISPLAY GREEN BACKGROUND ACCURACY 0 5 OF FULL SPAN SETTING ACCURACY ACTUAL SET VALUE COINCIDES WITH INDICATED SET VALUE RESPONSE SPEED RANGE 200 1 AMPLIFIER GAIN SLOW LOOP NORMAL 6 MAX HIGH 12 MAX DEAD BAND ADJUSTABLE FROM 0 TO 5 OF FULL SPAN INPUT RESISTANCE TO CURRENT LOOP 100 OHMS X CURRENT 0 7 VOLTS AMBIENT TEMPERATURE 4 F...

Page 3: ...3 PMC CONTROLLER MOUNTING DIMENSIONS INCHES MM A C Power Electrical Signal Input Output Pneumatic Input 100 psi Max Vent Pneumatic Output FIGURE 1 ...

Page 4: ...current flows into terminal 5 and terminal 4 is negative See Figure 4 A Introduction The Leslie PMC 1 electro pneumatic controller can be used to control pressure temperature liquid level and other process variables It accepts signals from any standard 4 20 mA transmitter and provides a pneumatic output to operate a diaphragm control valve etc It provides the following features 1 The controller su...

Page 5: ...remote location from a control valve 6 When the PMC 1 is being used as a temperature controller with an RTD an optional signal conditioning card calibrated for a temperature range suitable for the process must be installed in TB 5 Jumper at J5 J6 must be on J6 See figure 7 For a 3 wire RTD connect the two RTD wires that are internally connected together zero resistance between them to terminals 16...

Page 6: ...ated to read 25 0 when the CALIBRATE LO LED is lit and 175 0 when the CALIBRATE Hl LED is lit J7 0 000 to 1 999 J8 00 00 to 19 99 J9 000 0 to 199 9 J10 0000 to 1999 10 Using one of the pressure sensitive labels supplied label the display to indicate the unit of measurement for your process i e pressure temperature gpm etc 11 Adjust the air supply pressure to the controller by adjusting the filter ...

Page 7: ...lack Red TB 2 Approximate resistance 0 Ω Approximate resistance 75 F 109 Ω Unused terminal not connected 3 Wire RTD Head Wiring Connections for Two Wire RTD temperature Jump Black RTD lead Red RTD lead Terminal colored red or other contrasting color NOTE Jumper J5 J6 must be on J6 ...

Page 8: ... cable that the shielding is connected to the earth ground 4 Insufficient air pressure to PMC 1 a Make sure that the air pressure supplied to the PMC 1 is sufficient to fully stroke the control valve or to provide the maximum outlet pressure required from a regulator 5 Leaks in pneumatic lines a Small pneumatic line leaks can cause control instability particularly when using the PMC 1 with a regul...

Page 9: ...ED AND EXTERNAL POWER CAN BE BROUGHT TO THE SOLENOIDS AT TB 2 PIN 14 J5 JUMP WHEN EXTERNAL 4 20MA PROCESS FEEDBACK TRANSMITTER IS USED OR J6 JUMP WHEN RTD SIGNAL CONDITONAL CARD IS INDSTALLED IN THE PMC 1 J7 DECIMAL POINT SELECT REFER TO SECTION D PARA 7 J8 DECIMAL POINT SELECT REFER TO SECTION D PARA 7 J9 DECIMAL POINT SELECT REFER TO SECTION D PARA 7 J10 DECIMAL POINT SELECT REFER TO SECTION D P...

Page 10: ... Resistance x Current Voltage 100 x 020 0 7 Voltage 2 7 Volts Thus at 20mA the voltage drop of the PMC s transmitter loop is 2 7 volts EXAMPLE The PMC 1 is being used in a level control application The differential pressure transmitter used to measure the level has a minimum power requirement of 12 volts A chart recorder with an impedance resistance of 450Ω is being considered for use with the lev...

Page 11: ...l 3 receives the 4 20mA signal back 11 Terminal 2 is an earth ground A 4 wire transmitter needs two additional wires because it receives its power from a separate power source This type of transmitter can also be used with the PMC 1 and it is connected as shown in Figure 9 Since it receives its power from a separate source terminal 1 the PMC 1 s power is not used The 4 20mA signal from the transmi...

Page 12: ...alled in the PMC 1 is a variable voltage signal The signal conditioning card converts the voltage signal into a 4 20mA signal which can be used by the PMC 1 The wire connecting the RTD to the PMC 1 provides additional resistance which varies according to the gauge and length of the wire Although the additional resistance of the wire is insignificant over short distances it can affect accuracy over...

Page 13: ... cases the arrangement shown above is recommended A standard three way solenoid valve is installed in the air line between the PMC 1 and the control valve The solenoid is energized from the same power source used by the PMC 1 When the solenoid is energized ports B and C are connected and the pneumatic circuit between the PMC 1 and control valve is complete On loss of power the solenoid is no longe...

Page 14: ...oning card to the set point and using a series of short pneumatic pulses modulates the control valve as required to maintain the set point The PMC 1 s slow loop control mode can be selected for enhanced control in systems that respond slowly to control valve changes During installation the PMC 1 is calibrated by dialing in the upper and lower limits of the signal conditioning card The set point an...

Page 15: ...solating valve The isolating valve provides the ability to change or calibrate the pressure transmitter without otherwise disturbing the system The pig tail is important in steam applications to avoid overheating the pressure transmitter The loop in the pig tail maintains a condensate buffer between the steam and the sensing diaphragm of the pressure transmitter During installation the PMC 1 is ca...

Page 16: ...ine measures the static pressure in the system and acts as a reference point the difference between the upper and lower sensing lines is the head pressure of the liquid In an open system the reference line is vented to atmosphere A three valve manifold is recommended for use with the dp transmitter to facilitate isolation of the transmitter for replacement or in line calibration During installatio...

Reviews: