background image

point signal with five selectable defaults in case of loss of
external set point signal.

“REM/LOC”   Controller will default to Local set point control.
“REM/LPOS” Default to the last valve position prior to loss of signal.
“REM/VENT” Vent air from actuator on loss of signal.
“REM/LOAD” Load air into the actuator on loss of signal.
“REM/ZERO” Default to “ZERO” set point on loss of signal.
5)

If the PMC-1 is being used for controlling slow reacting
processes like temperature and level, select the control for-
mat for slow-acting control loops by moving the process
speed switch to the “SLOW” position. (See figure 7). For
fast processes (like pressure control) switch the process
speed switch to the “FAST’ position. For control loops
other than pressure, temperature, or level, install the
PMC-1 with the control format that will be most suited to
the control system’s reaction to control valve change.

6)

For initial adjustment, turn the response knob to mid
position, and dead band to position 0.5.

7)

Connect the appropriate jumper, as shown in Figure 7 to
locate the decimal point for maximum resolution of the
display in relation to the input transmitter. (The PMC-1
is shipped with the jumper at J10). The following table
shows the range of the display at each jumper position.

The LCD display reads the value of the selected mode as
indicated by the lit LED.
EXAMPLE: If the PMC-1 controller is being used to
control pressure, and the pressure transmitter is
calibrated for a range of 0-100 psig, then the maximum
resolution will be achieved by placing the decimal point
between the third and fourth digits (J9), so that the
display will read “100.0” at full scale.

8)

Replace the field wiring cover and turn on the external
electrical power.

9)

Display calibration using mode selection button.
The display can be calibrated in a range from-1000 to
+1999 units. A decimal point can be placed after the
second, third or fourth digit. If a change is required,
turn off the external power, then see step 7, above.
a) Press the mode selection button until the “Calibrate

LO” LED is lit. Using a small screw driver supplied
with the unit adjust the “LO” potentiometer on the
front of the panel so that the display indicates the
bottom range of the transmitter.

b) Press the mode selection button until the “Calibrate

Hl” LED is lit. Adjust the “HI” potentiometer on the
front of the panel so that the display indicates the top
range of the transmitter.

EXAMPLE ONLY: DO NOT CALIBRATE TO THESE

VALUES. If the PMC-1 controller is being used to
control temperature, and the RTD with optional
circuit card is calibrated for -25 deg. C to +175 deg. C,
then the display must be calibrated to read “-25.0”
when the “CALIBRATE LO” LED is lit, and “175.0”
when the “CALIBRATE Hl” LED is lit.

J7 = 0.000 to ±1.999
J8 = 00.00 to ±19.99
J9 = 000.0 to ±199.9

J10 = 0000  to ±1999

10) Using one of the pressure sensitive labels supplied, label

the display to indicate the unit of measurement for your
process, i.e. pressure, temperature, gpm, etc.

11 ) Adjust the air supply pressure to the controller by

adjusting the filter/regulator. The pressure should be set
5 to 10 psig higher than required to operate the
diaphragm control valve. Do not exceed 100 psig or the
rating of the equipment served, whichever is less.

12) Push the mode select button until the “SP” LED lights

up. Using the up/down buttons, adjust LCD display
observing operation of the diaphragm control valve. If it
does not move in the proper direction use the
direct/reverse switch (SW3) to obtain desired operation
of the valve.

13) Adjust the set point to move the control valve to the

closed position.

14) The system can now be started.

WARNING 

- This instruction can not cover the

safety precautions and procedures required for safe
start-up of every system. Make sure you understand
the system and its safe operation before start-up.

15) For bumpless transfer, move the auto/manual switch to

the manual position. Select the “SP” (set point) mode
and adjust to desired set point. Select the ‘PV’’ (process
value) mode. Using the load or vent buttons, adjust the
system until the display agrees with the set point. Move
the auto/manual switch to the auto position for
continued automatic control.

16) Adjust response speed and dead band to provide stable

control. Maximum speed and minimum dead band will
provide the highest accuracy but the system may cycle.
It’s best to adjust the response speed and dead band at
minimum and maximum system flows.

Initial Tunlng

17) Adjust response speed and dead band as follows:

Temperature or level control Speed of response

3.0

Dead band

.5

If temperature or level cycles, reduce speed of response.
If no cycling is occurring, keep increasing speed or
response until cycling begins, then back off half a unit.
Pressure or flow control

Speed of response

6.0

Dead band

.5

If pressure or flow cycles, reduce speed of response. If no
cycling is occurring, keep increasing speed of response
until cycling occurs, then back off half a unit.
The ideal tuning of the PMC-1 would be the maximum
speed of response and minimum dead band setting you
can use without the system going into constant
oscillation after an upset. 

E. Troubleshooting—General

1)

System cycles
a) Make sure Pneumatic connections from PMC-1 to the

valve are leak free. (Check with soapy water)

b) Adjust dead band and response speed. (See step 17 of

start-up instructions).

c) Check that the diaphragm control valve is operating

within its rated flow rangeability (usually 10-90%
open) and valve stem doesn’t stick.

6

Summary of Contents for PMC-1

Page 1: ...AND MAINTENANCE INSTRUCTIONS DIAGRAMS PARTS LIST 12501 Telecom Drive Tampa FL 33637 PMC 1 ELECTRO PNEUMATIC CONTROLLER T A B L E O F C O N T E N T S Specifications 2 Introduction 4 Operation 4 Installation 4 Pneumatic Connections 4 Field Wiring 4 Start Up 5 Troubleshooting 6 ...

Page 2: ...TION NO AIR CONSUMPTION AT STEADY STATE DISPLAY 3 1 2 DIGIT LCD BACKLIT DISPLAY GREEN BACKGROUND ACCURACY 0 5 OF FULL SPAN SETTING ACCURACY ACTUAL SET VALUE COINCIDES WITH INDICATED SET VALUE RESPONSE SPEED RANGE 200 1 AMPLIFIER GAIN SLOW LOOP NORMAL 6 MAX HIGH 12 MAX DEAD BAND ADJUSTABLE FROM 0 TO 5 OF FULL SPAN INPUT RESISTANCE TO CURRENT LOOP 100 OHMS X CURRENT 0 7 VOLTS AMBIENT TEMPERATURE 4 F...

Page 3: ...3 PMC CONTROLLER MOUNTING DIMENSIONS INCHES MM A C Power Electrical Signal Input Output Pneumatic Input 100 psi Max Vent Pneumatic Output FIGURE 1 ...

Page 4: ...current flows into terminal 5 and terminal 4 is negative See Figure 4 A Introduction The Leslie PMC 1 electro pneumatic controller can be used to control pressure temperature liquid level and other process variables It accepts signals from any standard 4 20 mA transmitter and provides a pneumatic output to operate a diaphragm control valve etc It provides the following features 1 The controller su...

Page 5: ...remote location from a control valve 6 When the PMC 1 is being used as a temperature controller with an RTD an optional signal conditioning card calibrated for a temperature range suitable for the process must be installed in TB 5 Jumper at J5 J6 must be on J6 See figure 7 For a 3 wire RTD connect the two RTD wires that are internally connected together zero resistance between them to terminals 16...

Page 6: ...ated to read 25 0 when the CALIBRATE LO LED is lit and 175 0 when the CALIBRATE Hl LED is lit J7 0 000 to 1 999 J8 00 00 to 19 99 J9 000 0 to 199 9 J10 0000 to 1999 10 Using one of the pressure sensitive labels supplied label the display to indicate the unit of measurement for your process i e pressure temperature gpm etc 11 Adjust the air supply pressure to the controller by adjusting the filter ...

Page 7: ...lack Red TB 2 Approximate resistance 0 Ω Approximate resistance 75 F 109 Ω Unused terminal not connected 3 Wire RTD Head Wiring Connections for Two Wire RTD temperature Jump Black RTD lead Red RTD lead Terminal colored red or other contrasting color NOTE Jumper J5 J6 must be on J6 ...

Page 8: ... cable that the shielding is connected to the earth ground 4 Insufficient air pressure to PMC 1 a Make sure that the air pressure supplied to the PMC 1 is sufficient to fully stroke the control valve or to provide the maximum outlet pressure required from a regulator 5 Leaks in pneumatic lines a Small pneumatic line leaks can cause control instability particularly when using the PMC 1 with a regul...

Page 9: ...ED AND EXTERNAL POWER CAN BE BROUGHT TO THE SOLENOIDS AT TB 2 PIN 14 J5 JUMP WHEN EXTERNAL 4 20MA PROCESS FEEDBACK TRANSMITTER IS USED OR J6 JUMP WHEN RTD SIGNAL CONDITONAL CARD IS INDSTALLED IN THE PMC 1 J7 DECIMAL POINT SELECT REFER TO SECTION D PARA 7 J8 DECIMAL POINT SELECT REFER TO SECTION D PARA 7 J9 DECIMAL POINT SELECT REFER TO SECTION D PARA 7 J10 DECIMAL POINT SELECT REFER TO SECTION D P...

Page 10: ... Resistance x Current Voltage 100 x 020 0 7 Voltage 2 7 Volts Thus at 20mA the voltage drop of the PMC s transmitter loop is 2 7 volts EXAMPLE The PMC 1 is being used in a level control application The differential pressure transmitter used to measure the level has a minimum power requirement of 12 volts A chart recorder with an impedance resistance of 450Ω is being considered for use with the lev...

Page 11: ...l 3 receives the 4 20mA signal back 11 Terminal 2 is an earth ground A 4 wire transmitter needs two additional wires because it receives its power from a separate power source This type of transmitter can also be used with the PMC 1 and it is connected as shown in Figure 9 Since it receives its power from a separate source terminal 1 the PMC 1 s power is not used The 4 20mA signal from the transmi...

Page 12: ...alled in the PMC 1 is a variable voltage signal The signal conditioning card converts the voltage signal into a 4 20mA signal which can be used by the PMC 1 The wire connecting the RTD to the PMC 1 provides additional resistance which varies according to the gauge and length of the wire Although the additional resistance of the wire is insignificant over short distances it can affect accuracy over...

Page 13: ... cases the arrangement shown above is recommended A standard three way solenoid valve is installed in the air line between the PMC 1 and the control valve The solenoid is energized from the same power source used by the PMC 1 When the solenoid is energized ports B and C are connected and the pneumatic circuit between the PMC 1 and control valve is complete On loss of power the solenoid is no longe...

Page 14: ...oning card to the set point and using a series of short pneumatic pulses modulates the control valve as required to maintain the set point The PMC 1 s slow loop control mode can be selected for enhanced control in systems that respond slowly to control valve changes During installation the PMC 1 is calibrated by dialing in the upper and lower limits of the signal conditioning card The set point an...

Page 15: ...solating valve The isolating valve provides the ability to change or calibrate the pressure transmitter without otherwise disturbing the system The pig tail is important in steam applications to avoid overheating the pressure transmitter The loop in the pig tail maintains a condensate buffer between the steam and the sensing diaphragm of the pressure transmitter During installation the PMC 1 is ca...

Page 16: ...ine measures the static pressure in the system and acts as a reference point the difference between the upper and lower sensing lines is the head pressure of the liquid In an open system the reference line is vented to atmosphere A three valve manifold is recommended for use with the dp transmitter to facilitate isolation of the transmitter for replacement or in line calibration During installatio...

Reviews: