Commissioning Menu Screen 16:
Maximum Alarm Temperature for Temperature Sensor #8
Pressing
▼
15 times displays
Commissioning Temp 8 max: 185F
This is the maximum temperature for RTD probe T8. Any temperature above this setting at
T8 will trigger an error message. Default setting is 185˚F
19
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
THERMAL DISINFECTION
WARNING: The Nucleus Digitally Controlled Mixing Valve is equipped with the ability to program the
valve to move to full hot position, which will allow ONLY high temperature hot supply water to enter
the device and subsequently deliver that high temperature water downstream of the device. There is
inherent risk in this procedure and it is a feature which allows the user to ‘Disinfect’ the plumbing
system downstream of the device.
Commissioning Menu Screen 17:
Thermal Disinfection
Pressing
▼
16 times displays
Commissioning Disinfect: N or Y
BEFORE THIS MODE IS ENGAGED, AN AUTHORIZED USER MUST BE AWARE OF THE POTENTIAL RISKS
TO END USERS DOWNSTREAM OF THIS DEVICE, AND MUST ALSO MAKE PROVISIONS TO PUT SAFETY
MEASURES IN PLACE DURING THE DISINFECTION STAGE TO ENSURE USER SAFETY.
SEVERE BURNS, SEVERE INJURY AND/OR EVEN DEATH MAY OCCUR IF SUCH PROVISIONS ARE NOT IN
PLACE WHEN SELECTING ‘Y’ ON THIS MENU!