Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17
33
5
Installation
5.2
Electrical installation
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5.2.5
External voltage supply
The communication module can be externally supplied with voltage via separate supply cables at
the 2-pin plug connector
X258
.
The external voltage supply of the communication module is necessary if the power supply for the
basic device fails but communication via the fieldbus is to be maintained.
The parameters of a standard device separated from the mains cannot be accessed.
Wiring of the X258 plug connector
[5-11] Wiring of the 2-pin plug connector with spring connection
How to wire the plug connector with spring connection:
1. Press a screwdriver into the notch below the terminal and keep it pressed.
2. Place the supply cable in the terminal.
3. Remove the screwdriver from the notch.
Assignment of the X258 plug connector
Note!
With external voltage supply, always use a separate power supply unit, safely separated
to EN 61800-5-1 in every control cabinet (SELV/PELV).
Stop!
Only wire the plug connector if the standard device is disconnected from the mains.
E84AYCXX010
Name
Description
+
U = 24 V DC (20.4 V - 0 % ... 28.8 V + 0 %)
I = 140 mA
-
Reference potential for the external voltage supply