45
6
Commissioning
6.4
Setting the IP configuration of the Inverter Drive 8400
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.4.2
Setting via codes in the »Engineer«
You can also set the IP parameters manually in the »Engineer« under the
Settings
tab. The values
will be transferred to the corresponding codes.
How to activate changed settings in the »Engineer«:
1. Execute device command
C00002 = "11: Save all parameter sets"
.
The current IP configuration is stored in the memory module of the drive.
2. Carry out a "Type 0 reset" for the
of the node, or switch the
voltage supply of the communication module off and on again.
Settings / Display
Description
Rotary coding switch
Display of the value set by means of the rotary coding switches (
).
Setting node addresses by means of rotary coding switches (
IP Config Control
) of how the IP configuration is to be made:
•
0
: The IP configuration currently stored in the communication module is
used.
•
1
: The IP configuration is assigned by a BOOTP server using the BOOTP.
•
2
: The IP configuration is assigned by a DHCP server using the DHCP.
IP Address
Setting of the IP address (
Subnet mask
Setting of the subnet mask (
)
Gateway Address
Setting of the gateway address (
Multicast IP Start Address
Setting of the Multicast IP start address (
Setting the multicast configuration (
Multicast Config TTL Value
Setting of the multicast TTL value (