8
I/O data transfer (implicit messages)
8.5
I/O configuration with »RSLogix 5000« version 19 or lower
70
Lenze · E84AYCEO communication module (EtherNet/IP™) · Communication Manual · DMS 3.0 EN · 10/2013 · TD17
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
5. Go to the "New Module" dialog window and define the properties of the newly added
device .
The terms "input" and "output" refer to the point of view of the scanner:
• Assembly input objects (input) are sent from the adapter to the scanner.
• Assembly output objects (output) are sent from the scanner to the adapter.
Settings for Lenze technology applications or user-definable parameter sets:
If you use a Lenze technology application or an individual parameter set in the drive, you
can exchange up to 16 user-definable words (INT) via the ports MCI_IN and MCI_OUT using
the assembly object instances
"Input = 111"
and
"Output = 110"
.
Go to
"Configuration" and enter the
Assembly instance "130"
and the
Size "0"
.