Error messages
Possible causes and remedies
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
Module parameter access failure [0x01bc6102]
Slave 1 data exchange timeout [0x01bc813a]
Slave 1 CTT2 extended cyclic timeout [0x01bc813b]
Slave 2 data exchange timeout [0x01bc813c]
Response
(Lenze setting printed in bold)
/
(
adjustable response)
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
warning
Information
Cause
Remedy
• AS-i voltage supply interrupted.
• Connection between the Communication Unit and
the Drive Unit defective.
• Check wiring and terminals.
• Switch the voltage supply of the AS-i network off and
on again.
• If this error continues to occur, please contact the
Lenze Service. (if required, the Communication Unit
must be replaced.)
Response
(Lenze setting printed in bold)
/
(
adjustable response)
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
warning
Information
Cause
Remedy
• AS-i communication / voltage supply interrupted.
• The monitoring time is too low.
• Check wiring and terminals.
• Switch the voltage supply of the AS-i network off and
on again.
• Check and raise the monitoring time.
• Check and adjust the AS-i settings of the master.
• Check and adjust the AS-i profile settings of the
master and the slaves.
Response
(Lenze setting printed in bold)
/
(
adjustable response)
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
warning
Information
Cause
Remedy
• AS-i communication / voltage supply interrupted.
• The monitoring time is too low.
• Check wiring and terminals.
• Switch the voltage supply of the AS-i network off and
on again.
• Check and raise the monitoring time.
• Check and adjust the CTT2 settings of the master.
• Check and adjust the AS-i profile settings of the
master and the slaves.
Response
(Lenze setting printed in bold)
/
(
adjustable response)
None
System fault
Fault
Trouble
Quick stop by trouble
Warning locked
warning
Information
Cause
Remedy
• AS-i communication / voltage supply interrupted.
• The monitoring time is too low.
• Check wiring and terminals.
• Switch the voltage supply of the AS-i network off and
on again.
• Check and raise the monitoring time.
• Check and adjust the AS-i settings of the master.
• Check and adjust the AS-i profile settings of the
master and the slaves.