Commissioning
How to configure the host (master)
26
Lenze · Decentralised frequency inverter 8400 motec (AS-Interface option) · EDS84DMOTASI EN 5.0 - 02/2019
_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _
6.2
How to configure the host (master)
Communication with the inverter first requires configuration of the host (master).
Defining the user data length
• The AS-Interface Communication Unit supports the configuration of max. 8 process data words
(max. 64 bytes).
• The user data length is defined during the initialisation phase of the master.
• The user data lengths for process input data and process output data are identical.
Note!
Observe the direction of the information flow.
• Process input data (Rx data):
Process data from the inverter (slave) to the host (master)
• Process output data (Tx data):
Process data from the host (master) to the inverter (slave)