23 RG-TDMOD
Drive Control & Communication
Parameter No.
1
Tmd Register #
(hexadecimal
representation)
Parameter Name
Range of Adjustment
Modbus value (decimal value)
Factory
Default
PV503
C52
86 (56H)
Motor Voltage
0 - 255%
Read Only
C53
87 (57H)
DC Bus Voltage
0 - 255%
Read Only
C54
88 (58H)
Motor Current
0 - 255%
Read Only
C56
89 (59H)
Drive Load
0 - 255%
Read Only
C57
90 (5AH)
Motor Torque
0 - 400%
Read Only
91 (5BH)
RESERVED
C61
92 (5CH)
Heatsink Temperature
0 - 255 °C
Read Only
C65
93 (5DH)
Vector Speed Loop Gain
0 - 1000 (0.0 - 100)
30.0
C66
94 (5EH)
Vector Speed Stability
0 - 1000 (0.0 - 100)
30.0
95 (5FH)
Not Used
96 (60H)
RESERVED
97 (61H)
RESERVED
98 (62H)
RESERVED
99 (63H)
RESERVED
C77
100 (64H)
Imax Gain
0 - 1600 (0.00 - 16.0)
(2)
0.25
C78
101 (65H)
Integral Action Time
12 - 9990 ms
65 ms
C84
102 (66H)
Motor Stator Resistance
0 - 6400 (0.00 - 64.0
W
)
(2)
0.00
W
C86
103 (67H)
Motor Rated Power
0 - 9990 (0.00 - 99.9 kW)
(2)
C87
104 (68H)
Motor Rated Speed
300 - 65000 RPM
1390 RPM
C88
105 (69H)
Motor Rated Current
0 - 4800 (0.0 - 480 A)
0.0 A
C89
106 (6AH)
Motor Rated Frequency
10 - 999 Hz
50 Hz
C90
107 (6BH)
Motor Rated Voltage
0 - 600 V
0 V
C91
108 (6CH)
Motor Cosine Phi
40 - 100 (0.40 - 1.00)
(2)
0.80
C92
109 (6DH)
Motor Stator Inductance
0 - 20000 (0.0 - 2000 mH)
0.0 mH
C93
110 (6EH)
Drive Identification
C94
111 (6FH)
User Password
0 - 999
0
112 (70H)
RESERVED
113 (71H)
RESERVED
C99
114 (72H)
Software Version
Read 4 words (fromat 'TMD 1.20')
Read Only
c01
115 (73H)
Acceleration Time 2
0 - 9990 (0.0 - 999 sec)
5.0 sec
c03
116 (74H)
Deceleration Time 2
0 - 9990 (0.0 - 999 sec)
5.0 sec
c06
117 (75H)
Holding Time - Auto
DC Injection Brake
0 - 9990 (0.0 - 999 sec)
0.0 sec
c08
118 (76H)
Analog Output Scaling
0 - 9990 (0.0 - 999)
100.0
119 (77H)
RESERVED
1 = The drive's programming code number; (2) = Two decimal places assumed.