PDU description
Plug
Outlet
Rating
DPI 32 amp / 250 V three-
phase Enterprise C19 / C13
PDU+ (or PDU) with IEC 309
3P+N+Gnd connector
L1
L2
L3
N
G
N
L1
L2
L3
G
32 amps, 250 V ac IEC 309 3P
+N+Gnd
DPI 32 amp / 250 V single-
phase Enterprise C19 / C13
PDU+ (or PDU) with IEC 309
P+N+Gnd connector
N
L
G
N
L
G
32 amps, 250 V ac IEC 309 P
+N+Gnd
DPI 63 amp / 250 V single-
phase Enterprise C19 / C13
PDU+ (or PDU) with IEC 309
P+N+Gnd connector
N
L
G
N
L
G
63 amps, 250 V ac IEC 309 P
+N+Gnd
DPI 30 amp / 208 V single-
phase Enterprise C19 / C13
PDU+ (or PDU) with NEMA
L6-30P (2P+Gnd) connector
G
X
Y
G
X
Y
30 amps, 250 V ac NEMA L6-
30P (2P+Gnd)
DPI 60 amp / 208 V single-
phase Enterprise C19 / C13
PDU+ (or PDU) with IEC 309
2P+Gnd connector
L2
L1
G
L2
L1
G
48 amps, 250 V ac IEC 309 2P
+Gnd
Chapter 8
.
PDU specifications
57
Summary of Contents for 46M4002
Page 1: ...1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 24: ...16 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 30: ...22 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 34: ...26 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 56: ...48 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 60: ...52 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 62: ...54 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 68: ...60 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 70: ...62 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 74: ...66 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 85: ......
Page 86: ......