Weight(not including power cord)
6.3 kg (13.8 lb)
Weight of power cord (approximate, varies by PDU model)
5.4 kg (11.8 lb)
Operating temperature at 0 - 914 m (0 - 3000 ft)(room ambient)
10°C - 60°C (50°F - 140°F)
Operating temperature at 914 -2133 m (3000 - 7000 ft) (room
ambient)
10°C - 60°C (50°F - 140°F)
Operating humidity
8% - 80% (noncondensing)
Localized air temperature in PDU
60°C (140°F) maximum
Rated voltage, rated current
1. 220 - 240 V ac, 32 amps, single-phase
2. 200 - 208 V ac, 48 amps, single-phase
3. 220 - 240 V ac, 63 amps, single-phase
4. 220 - 240 V ac, 32 amps, three-phase Wye
5. 200 - 208 V ac, 24 amps, single-phase
6. 200 - 208 V ac, 48 amps, three-phase Delta
7. 200 - 208 V ac, 48 amps, single-phase
8. 220 - 240 V ac, 63 amps, single-phase
9. 220 - 240 V ac, 32 amps, three-phase Wye
10. 200 - 208 V ac, 48 amps, three-phase Delta
11. 220 - 240 V ac, 32 amps, single-phase
12. 200 - 208 V ac, 24 amps, single-phase
13. 220 - 240 V ac, 30 amps, single-phase
Maximum power rating
1. 7680 VA
2. 9984 VA
3. 15120 VA
4. 23040 VA
5. 4992 VA
6. 17292 VA
7. 9984 VA
8. 15120 VA
9. 23040 VA
10. 17292 VA
11. 7680 VA
12. 4992 VA
13. 7200 VA
Rated frequency
50 - 60 Hz
Circuit breakers
Nine double-pole branch rated circuit breakers rated at 20 amps for 1U C19 PDU modelsSix double-
pole branch rated circuit breakers rated at 20 amps for 1U C13 PDU models
Power outlets
For C19 PDU models:
Nine IEC 320 - C19 outlets rated at 16 amps (VDE) / 20 amps (UL/CSA) and Three IEC 320 - C13 outlets rated at 10
amps (VDE) / 15 amps (UL/CSA)
For 1U C13 PDU models:
Twelve IEC 320 - C13 outlets rated at 10 amps (VDE) / 15 amps (UL/CSA)
You must connect the connector on the power cord that comes with the PDU to a properly wired and
grounded outlet. The following table shows illustrations of the power cord connector (plug) and the correct
outlet for each of the PDUs.
56
1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide
Summary of Contents for 46M4002
Page 1: ...1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 24: ...16 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 30: ...22 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 34: ...26 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 56: ...48 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 60: ...52 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 62: ...54 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 68: ...60 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 70: ...62 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 74: ...66 1U C19 and C13 Switched and Monitored PDUs Installation and Maintenance Guide ...
Page 85: ......
Page 86: ......